Carrier WeatherMaster 50HC14 Installation Instructions Manual page 31

Single package rooftop cooling only unit with puron (r-410a) refrigerant
Table of Contents

Advertisement

MENU
PARAMETER
INSTALL
UNITS DEG
EQUIPMENT
AUX2 IN
FAN SPEED
SYSTEM
SETUP
FAN CFM
AUX1 OUT
OCC
FACTORY DEFAULT
MA LO SET
FREEZE POS
CO2 ZERO
CO2 SPAN
STG3 DLY
ADVANCED
SETUP
SD DMPR POS
DA LO ALM
DA HI ALM
DCVCAL ENA
Table 8 — Menu Structure (cont)
PARAMETER
PARAMETER
DEFAULT
RANGE AND
VALUE
INCREMENT
01/01/10
N/A
F
F or C
Conventional or
CONV
HP
SD/W or HP(O)/
W
HP(B)
2 speed
1 speed/2 speed
100 to 15000 cfm;
5000cfm
increment by 100
NONE
ERV
NONE
EXH2
SYS
INPUT or
INPUT
ALWAYS
NO
NO or YES
35 to 55°F;
45 F
Incremented by 10
CLO
CLO or MIN
0 to 500 ppm;
0ppm
Increment by 10
1000 to 3000 ppm;
2000ppm
Increment by 10
0 min, 5 min, 15
min, then 15 min
2.0h
intervals. Up to 4
hrs or OFF
CLO
CLO or OPN
35 to 65°F; (2 to
45 F (7 C)
18°C) Incremented
by 5 deg.
70 to 180°F; (21 to
80 F (27 C)
82°C) Incremented
by 5 deg.
MAN (manual)
MAN
AUTO
31
NOTES
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
Sets economizer controller in degrees Fahrenheit or Celsius
CONV = conventional;
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump
input from thermostat or controller.
See Menu Note 7.
In CONV mode:
SD + Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV
mode for W. Shutdown is not available in 2-speed fan mode.
See Menu Note 7.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat.
Sets the economizer controller for operation of 1 speed or 2
speed supply fan.
NOTE: 2-speed fan option also needs Heat (W1) programmed in
AUX 2 In. See Menu Note 7.
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVAL ENA = AUTO
The value is found on the nameplate label for the specific unit.
Select OUTPUT for AUX1 O relay
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator
• EXH2 = second damper position relay closure for second
exhaust fan
• SYS = use output as an alarm signal
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac),
the 24 vac is input "INPUT" to the OCC terminal. If no occupancy
output from the thermostat then change program to "ALWAYS"
OR add a jumper from terminal R to OCC terminal.
Resets all set points to factory defaults when set to YES. LCD
will briefly flash YES and change to NO but all parameters will
change to the factory default values.
NOTE: RECHECK AUX2 IN and FANTYPE for required 2-speed
values.
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and
alarm if temperature falls below setup value).
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active (closed or MIN
POS).
CO
ppm level to match CO
sensor start level.
2
2
CO
ppm span to match CO
sensor.
2
2
COOLING STAGE 3 DELAY
Delay after stage 2 cool has been active. Turns on 2nd stage of
cooling when economizer is 1st stage and mechanical cooling is
2nd stage. Allows three stages of cooling, 1 economizer and 2
mechanical.
OFF = no Stage 3 cooling
Indicates shutdown signal from space thermostat or unitary
controller. When controller receives 24 vac input on the SD
terminal in conventional mode, the OA damper will open if
programmed for OPN and OA damper will close if programmed
for CLO. All other controls, e.g., fans, etc. will shut off.
Used for alarm for when the DA air temperature is too low. Set
lower range of alarm, below this temperature, the alarm will
show on the display.
Used for alarm for when the DA air temperature is too high. Set
upper range of alarm, above this temperature, the alarm will
show on the display.
Turns on the DCV automatic control of the dampers. Resets
ventilation based on the RA, OA, and MA sensor conditions.
Requires all 3 RA, OA, and MA sensors.