Carrier WeatherMaster 50HC14 Installation Instructions Manual page 28

Single package rooftop cooling only unit with puron (r-410a) refrigerant
Table of Contents

Advertisement

To use the keypad when working with menus:
Press the ▲ (Up arrow) button to move to the previous
menu.
Press the ▼ (Down arrow) button to move to the next
menu.
Press the
(Enter) button to display the first item in
the currently displayed menu.
Fig. 52 — W7220 Controller Navigation Buttons
Press the
(Menu Up/Exit) button to exit a menu's item
and return to the list of menus. To use the keypad when work-
ing with Setpoints, System and Advanced Settings, Checkout
tests and Alarms:
1.
Navigate to the desired menu.
2.
Press the
(Enter) button to display the first item in
the currently displayed menu.
3.
Use the ▲ and ▼ buttons to scroll to the desired param-
eter.
4.
Press the
(Enter) button to display the value of the
currently displayed item.
5.
Press the ▲ button to increase (change) the displayed
parameter value.
6.
Press the ▼ button to decrease (change) the displayed
parameter value.
NOTE: When values are displayed, pressing and holding the ▲
or ▼button causes the display to automatically increment.
7.
Press the
(Enter) button to accept the displayed value
and store it in nonvolatile RAM.
8.
"CHANGE STORED" displays.
9.
Press the
(Enter) button to return to the current menu
parameter.
10. Press the
(Menu Up/Exit) button to return to the pre-
vious menu.
MENU STRUCTURE
Table 8 illustrates the complete hierarchy of menus and
parameters for the EconoMi$er
The Menus in display order are:
STATUS
SETPOINTS
SYSTEM SETUP
ADVANCED SETUP
CHECKOUT
ALARMS
IMPORTANT: Table 8 illustrates the complete hierarchy.
Your menu parameters may be different depending on your
configuration.
For example if you do not have a DCV (CO
then none of the DCV parameters appear and only MIN
POS will display. If you have a CO
and DCV MAX will appear AND if you have 2 speed fan
DCV MIN (high and low speed) and DCV MAX (high and
low speed will appear).
NOTE: Some parameters in the menus use the letters MA or
MAT, indicating a mixed air temperature sensor location before
the cooling coil. This unit application has the control sensor lo-
cated after the cooling coil, in the fan section, where it is desig-
nated as (Cooling) Supply Air Temperature or SAT sensor.
SETUP AND CONFIGURATION
Before being placed into service, the W7220 Economizer
module must be setup and configured for the installed system.
IMPORTANT: During setup, the economizer module is live at
all times.
The setup process uses a hierarchical menu structure that
is easy to use. Press the ▲ and ▼ arrow buttons to move for-
ward and backward through the menus and press the button to
select and confirm setup item changes.
TIME-OUT AND SCREENSAVER
When no buttons have been pressed for 10 minutes, the
LCD displays a screen saver, which cycles through the Status
items. Each Status items displays in turn and cycles to the
next item after 5 seconds.
28
®
X system.