Carrier WeatherMaster 50HC14 Installation Instructions Manual page 19

Single package rooftop cooling only unit with puron (r-410a) refrigerant
Table of Contents

Advertisement

NOTICE/AVIS
Convenience Outlet Utilization
Maximum Intermittent Use 15 - Amps
Maximum Continuous Use 8 - Amps
Observe a 50% limit on the circuit
Loading above 8 - Amps
Utilisation de la prise utilitaire
Usage intermittent maximum 15 - Amps
Usage continu maximum 8 - Amps
Observez une limite de 50% sur le circuit
Chargement au-dessus de 8 - Amps
Fig. 32 — Convenience Utilization Notice
UNIT
CONNECT
VOLTAGE
AS
CONNECTIONS
L1: RED +YEL
208,230
240
L2: BLU + GRA
460
480
Splice BLU + YEL
575
600
Fig. 33 — Unit Powered Convenience Outlet Wiring
Fuse on power type
The factory fuse is a Bussman "Fusetron" T-15, non-re-
newable screw-in (Edison base) type plug fuse.
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Using unit-mounted convenience outlets: Units with unit-
mounted convenience outlet circuits will often require that
two disconnects be opened to de-energize all power to the
unit. Treat all units as electrically energized until the
convenience outlet power is also checked and de-
energization is confirmed. Observe National Electrical
Code Article 210, Branch Circuits, for use of convenience
outlets.
50HE501288
PRIMARY
TRANSFORMER
TERMINALS
H1 + H3
H2 + H4
L1: RED
H1
H2 + H3
L2: GRA
H4
L1: RED
H1
L2: GRA
H2
Installing Weatherproof Cover
A weatherproof while-in-use cover for the factory-in-
stalled convenience outlets is now required by UL standards.
This cover cannot be factory-mounted due to its depth; it
must be installed at unit installation. For shipment, the conve-
nience outlet is covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit's control box.
The kit includes the hinged cover, a backing plate and gasket.
DISCONNECT ALL POWER TO UNIT AND CONVE-
NIENCE OUTLET. LOCK-OUT AND TAG-OUT ALL
POWER.
2.0
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until ap-
proximately
/
1
the gasket over the screw heads. Slip the backing plate over the
screw heads at the keyhole slots and align with the gasket; tight-
en the two screws until snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as
shown in Fig. 34. Remove two slot fillers in the bottom of the
cover to permit service tool cords to exit the cover. Check for
full closing and latching.
COVER - WHILE-IN-USE
WEATHERPROOF
Fig. 34 — Weatherproof Cover Installation
HACR
The amp rating of the HACR factory-installed option is
based on the size, voltage, indoor motor and other electrical op-
tions of the unit as shipped from the factory. If field-installed
accessories are added or changed in the field (i.e., power ex-
haust), the HACR may no longer be of the proper amp rating
and therefore will need to be removed from the unit. See unit
nameplate and label on factory-installed HACR for the amp
rating of the HACR that was shipped with the unit from the
factory. See unit nameplates for the proper fuse, HACR or
maximum over-current protection device required on the unit
with field-installed accessories.
19
-in. (13 mm) under screw heads is exposed. Press
2
GFCI RECEPTACLE
BASEPLATE FOR
GFCI RECEPTACLE
NOT INCLUDED
GASKET

Advertisement

Table of Contents
loading

Table of Contents