F-2600 & F-2700 Series Vortex Flow Meter Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 www.onicon.com • sales@onicon.com 0808-11 / 19204 03-18...
Page 2
Messages identified as IMPORTANT NOTICE contain information critical to the proper operation of the product. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Page 3
When using toxic or corrosive gases, purge the line with inert gas for a minimum of four hours at full gas flow before installing the flow meter. For F-2700 series insertion flow meter installations, the sensor alignment pointer must point downstream in the direction of flow. The AC wire insulation temperature rating must meet or exceed 85° C (185° F) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204 Page...
Page 4
Incorporated. The information contained in this manual is subject to change without notice. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Energy flow with temperature and external pressure compensation and Net Energy using a second temperature sensor. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
10. Calculate the sensor probe insertion depth and insert the sensor probe into the pipe as described on the following pages. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
An insertion tool must be used for any installation where a flow meter is inserted under pressure greater than 50 psig. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Do not confuse this with possible interference in the pipe. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Do not confuse this with possible interference in the pipe. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
The sensor alignment pointer must point downstream, in the direction of flow. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
7. Tighten the screws. Replace the cover and set screw. Restore power to the meter. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
3. Tighten the three set screws. Restore power to the meter. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
(0.5 to 0.6 Nm). Use a separate conduit entry for signal lines to reduce the possibility of AC noise interference. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
In any case, the voltage of the frequency output is the same as the voltage supplied to the circuit. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
In any case, the voltage of the pulse output is the same as the voltage supplied to the circuit. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
RTD. If a second RTD is not being used, then the factory supplied 1000 ohm resistor needs to be installed in its place. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
5. Program the UNITS menu first because later menus will be based on the units selected. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Press EXIT and then ENTER to save changes and return to the Run Mode. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Up to three relay alarm outputs are available depending on meter configuration.) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Use the Totalizer #2 to monitor flow or energy. Note that Totalizer #2 does not operate a relay. It is for monitoring only. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
(These are global settings and determine what appears on all screens.) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Cutoff are set at the factory. Consult the factory for help with these settings if the meter is showing erratic flow rate. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Use the Password Menu to set or change the system password. The factory-set password is 1234. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
3-2:1-0, then each pair of characters will be transmitted in reverse order. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Page 85
16-bit register, then the value will likely be invalid. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Page 86
Alarm #2 state 10003 Alarm #3 state 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204 Page...
Page 88
00 50 Number of registers = 80 F0 36 CRC 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Page 89
00 00 Data to “turn off coil” does not reset totalizer CD CA CRC 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Page 90
The below table shows the implemented properties for each Vortex Mass Flow Meters object type. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
% Change to final value in one second = 100(1 -e (1/TC) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
3. Go to the first level of the Hidden Diagnostics and record the Pe(V) and Pv(V) values and consult the factory with findings. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Page 120
Note: Net energy meter requires one temperature sensor and one thermowell installation kit sized to pipe. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Page 121
Note: Net energy meter requires 1 temperature sensor and 1 thermowell installation kit sized to pipe. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Page 124
Where T is the temperature in Kelvin. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...
Page 126
The temperatures are all in degrees Rankin. Do not believe the subscript R means they are reduced temperatures. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com F-2600 & F-2700 Vortex Flow Meter Manual 03/18 - 0808-11 / 19204...