Modbus Register Address Information
40116
Reserved
40117
Temperature (Degrees C)
40118 to 40122
Reserved
40123 to 40131
Date and Time
40132
Sensor Type
40133 to 40136
Reserved
40137 to 40138
Microcontroller Operating Voltage
40139 to 40140
Microcontroller Reference Voltage
40141
BLE Connection Status
40142 to 40145
Reserved
40146 to 40152
Gas Name String
40153
Temperature (Degrees C)
40154
Temperature (Degrees F)
40155
Calibration Due
40156
Relay Status
40157
Supply Voltage
40158
Reserved
40159
Calibration Interval
40160
Alarm Type
40161
Inhibit Timeout
40162
Relay Configuration
R/W
Type
Size Description
R
u16
1
R
s16
1
Transmitter temperature
R
string[18]
9
Format is "mm/dd/yy hh:mm:ss"
R
u8
1
0x00 :ECC
0x01: FL CAT
0x02: IR
0x03: PID
0x04: MOS
R
f32
2
R
f32
2
R
u8
1
R
string[14]
7
R
s16
1
Transmitter temperature, duplicate
R
s16
1
R
u16
1
Calibration interval - DaysPassedSinceLastSuccessfulCal
R
u8
1
R
f32
2
The voltage supplied to the Sensepoint XCL/XRL at the nominal 24.0
volt input, in millivolts.
R
u16
1
R
u8
1
R
u16
1
R
u8
1
1011
Notes
0x00: Not connected, 0x01: Connected
High nibble : Relay 2 status
Low nibble : Relay 1 status
1 : Energized, 0 : De-energized
High nibble : Alarm 2 Type
Low nibble : Alarm 1 Type
0: Disable, 1: Rising, 2:Falling
Not used in Sensepoint XCL/XRL
Bit: 0 to 1: Relay Type 1 (0: Fault, 1: Alarm1, 2: Alarm2)
Bit: 2 to 3: Relay Type 2 (0:Fault, 1: Alarm1, 2: Alarm2)
Bit: 4 : Initial Relay Status 1 (0: De-energized, 1: Energized)
Bit: 5 : Initial Relay Status 2 (0: De-energized, 1: Energized)