Modbus Register Address Information
30001
Main SW Version of Instrument
30002
EEP Version of Instrument
30004 to 3009
Location String
30010
Modbus Slave ID
30011
Monitor Status
30012
Inhibit Current (mA)
30013
Reserved
30014
Active Alarm
30016 to 30017
Latched Alarm
30018 to 30019
Active Fault
30020 to 30021
Latched Fault
30022 to 30034
Location Tag
40101
System ID Code
40102
System ID Code
40103 to 40104
Gas Reading
40105
Fault and Warning
R/W
Type
Size Description
R
u8
1
R
u8
1
R
string[12]
6
R
u8
1
R
u16
1
R
u8
1
R
u16
1
R
u32
2
R
u32
2
R
u32
2
R
u32
2
R
string[26] 13
R
u16
1
MSB always 0x26 to facilitate automatic identification. LSB repeat of
Modbus address.
R
u16
1
Identical to 40101
R
f32
2
The reported gas concentration in current measurement units. For ex-
ample, methane at 50% LEL would be reported as 50.0 here.
This concentration is forced to last reading before switching into inhibit
mode during inhibit mode.
R
u8
1
This is the integer representation of the fault status. If any fault exists this
will take a value in the range 1200 to 1999. Otherwise, if any warning
exists, this will take a value in the range 1 to 999. Normally, this has the
value zero.
Notes
Not used in Sensepoint XCL/XRL
1 : Normal
2 : Warm Up after power on
3 : in Inhibit
12 : Calibration
Not used in Sensepoint XCL/XRL
bit 0 Alarm 1 is active
bit 1 Alarm 2 is active
bit 1 Alarm 3 is active (not used)
bit 0 Alarm 1 is latched
bit 1 Alarm 2 is latched
bit 2 Alarm 3 is latched (not used)
Upper Two Bytes: fault
Lower Two Bytes: warning
Bit 0 to Bit 15: warning
Bit 16 to Bit 31: fault
Not used
Location tag for BLE scanning
Upper Byte : Type Code : 0x26
Lower Byte : My Address
Upper Byte : Type Code : 0x26
Lower Byte : My Address : Dummy Spacer
Fault = 1200 + Number
Warning = Number as is