Commissioning - Honeywell Sensepoint XRL Instruction Manual

Fixed gas detector
Hide thumbs Also See for Sensepoint XRL:
Table of Contents

Advertisement

NOTE
The Sensepoint XRL gas detector is supplied from the factory
pre-calibrated. However, it is strongly recommended that the
detector response is checked and if necessary, re-calibrated before
placing it into service. Refer to
the correct calibration procedure.
There is a status indicator on the face of the gas detector. The operating
state of the detector is indicated by one of four colors, either steady or
flashing.
Normal: The indicator flashes green every 20 seconds when the
concentration of the target gas is within normal range.
NOTE
Using the mobile Sensepoint app, you can change how the green
indicator behaves during normal operation. Select between
confidence flash (default setting), steady green or off.
Warning: The indicator alternatively flashes green and yellow
when the gas detector is in a warning state.
Fault: The indicator flashes yellow when the gas detector is in a
fault state.
Chapter

Commissioning

Calibration
on page 33 for details on
3
27