Note On Adding Refrigerant - Pioneer YN-M Series Installation Manual

Multi-split system air conditioner / heat pump. inverter++ models two, three, four, and five zones (dual, triple, quad, and quint multi)
Hide thumbs Also See for YN-M Series:
Table of Contents

Advertisement

Note On Adding Refrigerant

CAUTION
• Refrigerant charging must be performed after wiring, vacuuming, and leak testing.
DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system.
Doing so can damage the unit or impact it's functioning.
• Charging with unsuitable substances may cause explosions or accidents. Ensure that only the
appropriate refrigerant (R410a) is used.
Refrigerant containers must be opened slowly. Always use protective gear when charging the system.
DO NOT mix refrigerants types.
N=2 (Two Zone models), N=3 (Three Zone models), N=4 (Four Zone models), N=5 (Five Zone models).
Depending on the length of connective piping, or the pressure of the evacuated system, you
may need to add refrigerant. Refer to the table below for refrigerant amounts to be added:
Connective Pipe
Air Purging
Length
If total pipe length is less
Vacuum Pump
than N x 7.5m (N x 25')
If total pipe length is more
Vacuum Pump
than N x 7.5m (N x 25'),
calculate the excess length
Note: The standard pipe length calculated for precharged value for each circuit is 7.5m (25').
Safety and Leakage Check
Electrical Safety Check
Perform the electrical safety check after
completing installation. Cover the following
areas:
1. Insulation resistance:
The insulation resistance must be more
than 2MΩ.
2. Grounding work:
After finishing grounding work, measure
the grounding resistance by visual detection
and using the grounding resistance tester.
Make sure the grounding resistance is less
than 4Ω.
3. Electrical leakage check (performed during
test while unit is on)
During a test operation, after completing
installation, use an electroprobe and
multimeter to perform an electrical leakage
check. Turn off the unit immediately if
leakage is detected. Try and evaluate different
solutions until the unit operates properly.
Page 26
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Method
Liquid Side: Ø 6.35 (Ø 1/4") 9K, 12K, 18K Indoor Units
For each m of excessive pipe length, add: 15g/m
For each ft. of excessive pipe length, add: 0.16oz/ft
Additional Refrigerant (
R410a)
Do not add Refrigerant
Liquid Side: Ø 9.52 (Ø 3/8") 24K Indoor Units
For each m of excessive pipe length, add: 30g/m
For each ft. of excessive pipe length, add: 0.32oz/ft
Gas Leak Check
1. Soapy water method:
Apply a soap-water solution, or a liquid
neutral detergent, on the indoor unit
connection, or outdoor unit connections,
with a soft brush to check for leakage of the
connecting points of the piping. If bubbles
emerge, the pipes are experiencing leakage.
2. Leak detector
Use a leak detector to check for leakage.
NOTE: The illustration is for example purposes
only. The actual order of A, B, C, D, and E on the
system may be slightly different from the unit
you purchased, but the general shape will remain
the same.
Indoor unit
check point
Outdoor unit
check point
A, B, C, D are points for the four zone type.
A, B, C, D, and E are points for the five zone type.
Fig. 9.4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents