Toshiba MMY-MAP0806HT8P-E Installation Manual page 79

Air conditioner (multi type)
Hide thumbs Also See for MMY-MAP0806HT8P-E:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
<Line (system) address>
2
Push the TEMP.
/
buttons
repeatedly to set the CODE No. to
3
Push the TIME
/
buttons repeatedly
to set a system address.
(Match the address with the address on the
interface P.C. board of the header outdoor unit in
the same refrigerant line.)
4
Push
button.
(It is OK if the display turns on.)
<Indoor unit address>
5
Push the TEMP.
/
buttons
repeatedly to set the CODE No. to
6
Push the TIME
/
buttons repeatedly
to set an indoor unit address.
7
Push the
button.
(It is OK if the display turns on.)
<Group address>
8
Push the TEMP.
/
buttons
repeatedly to set the CODE No. to
9
Push the TIME
/
buttons repeatedly
to set a group address. If the indoor unit
is individual, set the address to
header unit,
; follower unit,
Individual
: 0000
}
Header unit
: 0001
In case of group
Follower unit
: 0002
control
10
Push the
button.
(It is OK if the display turns on.)
11
Push the
button.
The address setting is complete.
(
flashes. You can control the unit after
has disappeared.)
155-EN
1117101201-3 EN.indd 78
1117101201-3 EN.indd 78
NOTE
1. Do not use address numbers 29 or 30 when setting
system addresses using the remote controller.
.
These 2 address numbers cannot be used on
outdoor units and the CODE No. [E04] (Indoor/
outdoor communication error) will appear if they are
mistakenly used.
2. If you set addresses to indoor units in 2 or more
refrigerate lines manually using the remote
controller and will control them centrally, set the
header outdoor unit of each line as below.
• Set a system address for the header outdoor unit
of each line with SW13 and 14 of their interface
P.C. boards.
• Turn off DIP switch 2 of SW30 on the interface
P.C. boards of all the header outdoor units
connected to the same central control, except the
.
unit that has the lowest address. (For unifying the
termination of the wiring for the central control of
indoor and outdoor units)
• Connect the relay connectors between the [U1,
U2] and [U3, U4] terminals on the header outdoor
unit of each refrigerate line.
• After finishing all the settings above, set the
address of the central control devices. (For the
setting of the central control address, refer to
the installation manuals of the central control
devices.)
.
;
.
Confirming the indoor unit
addresses and the position
of an indoor unit using the
remote controller
¿ Confirming the numbers and
positions of indoor units
To see the indoor unit address of an
indoor unit which you know the position of
q When the unit is individual (the indoor unit is
paired with a wired remote controller one-to-
one), or it is a group-controlled one.
CODE No.
UNIT No.
1
TEMP.
ON / OFF
Starts
TIMER SET
running
TIME
FILTER
RESET TEST
SET CL
2
(Execute it while the units are running.)
1
Push the
button if the units stop.
2
Push the
button (left side of the
button).
A unit numbers
is indicated on the LCD
(it will disappear after a few seconds).
The indicated number shows the system address
and indoor unit address of the unit.
When 2 or more indoor units are connected to
the remote controller (group-controlled units), a
number of other connected units appears each
time you push the
button (left side of the
button).
– 78 –
To find an indoor unit's position from its
address
q When checking unit numbers controlled as a
group
CODE No.
SET
DATA
SETTING
UNIT No.
R.C.
No.
TEMP.
ON / OFF
3
TIMER SET
1
TIME
FILTER
Stop
RESET TEST
SET CL
1
2
(Execute it while the units are stopped.)
The indoor unit numbers in a group are indicated one
after another. The fan and louvers of the indicated
units are activated.
1
Push and hold the
and
buttons at
the same time for more than 4 seconds.
appears on UNIT No. on the LCD display.
The fans and louvers of all the indoor units in
the group are activated.
2
Push the
button (left side of the
button). Each time you push the button,
the indoor unit numbers are indicated one
after another.
• The first-indicated unit number is the address
of the header unit.
• Only the fan and louvers of the indicated indoor
unit are activated.
3
Push the
button to finish the procedure.
All the indoor units in the group stop.
q To check all the indoor unit addresses using
an arbitrary wired remote controller.
(When communication wirings of 2 or more
refrigerant lines are interconnected for
central control)
156-EN
8/8/2559 BE 3:49 PM
8/8/2559 BE 3:49 PM