Pipe-diameter
Type
Draw-out forward
Gas
Liquid
Cut the L-shaped pipe at the horizontal
straight section, then braze the supplied
attachment pipe, and the socket, elbow
MAP180
Ø28.6
Ø15.9
and pipe procured locally.
MAP200
Liquid pipe
Attachment
pipe
Balance
pipe
MAP220
Ø28.6
Ø19.1
Pipe
Extruding margin of copper pipe with flare machining: B (Unit: mm)
Copper pipe outer
When using R410A
dia.
tool
9.5
12.7
0 to 0.5
15.9
19.1
Extruding margin of copper pipe with flare tools: A (Unit: mm)
Copper pipe outer
+0
A
dia.
−0.4
9.5
13.2
12.7
16.6
15.9
19.7
19.1
24.0
* When using the conventional flare tool, to connect R410A pipes with flaring, make a margin approx. 0.5mm
longer than that of an R22 pipe so that the flare size matches the one specified. It is convenient to use a copper
pipe gauge for size adjustment of the extruding margin.
CAUTION
Wrap the ball valve in a
wet cloth to keep it cool
and prevent the heat from
the torch from damaging it
when connecting the pipe
to the ball valve on the
gas line.
123-EN
1117101201-3 EN.indd 62
1117101201-3 EN.indd 62
Draw-out downward
Cut the L-shape pipe at the vertical straight
section, then braze the supplied attachment
pipe, and the socket and pipe procured
locally.
Gas
Liquid pipe
Gas pipe
pipe
Attachment
Gas pipe
Elbow
pipe
Socket
Attachment pipe
Attachment
Balance
Socket
pipe
pipe
Pipe
Socket
Section
Pipe
to be cut
Pipe
When using
conventional tool
1.0 to 1.5
Coupling size of brazed pipe
Connected section
External size
Internal size
G
K
Cloth
Torch
External size
Standard outer dia.
of connected
copper pipe
6.35
6.35 (±0.03)
9.52
9.52 (±0.03)
Gas
12.70
12.70 (±0.03)
pipe
15.88
15.88 (±0.03)
Section
19.05
19.05 (±0.03)
to be cut
22.22
22.22 (±0.03)
28.58
28.58 (±0.04)
34.92
34.90 (±0.04)
38.10
38.10 (±0.05)
41.28
41.28 (±0.05)
Selection of pipe materials and sizes
¿ Selection of pipe materials
Materials : Phosphorus deoxidation seam-less pipe
Minimum wall thickness for R410A application
Soft
Half hard or hard
OK
OK
OK
OK
No Good
No Good
No Good
No Good
No Good
¿ Capacity code of indoor and outdoor units
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of
connectable indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor
units differs based on the height difference between the indoor units.
• When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent
to HP) of the outdoor unit.
• When the height difference between the indoor units is over 15m: Up to 105% of the capacity code.
– 62 –
Connected section
Internal size
Min. depth of
Standard outer dia.
insertion
Oval value
(Allowable difference)
C
F
K
G
6.45 (
+0.04
)
7
6
0.06 or less
−0.02
9.62 (
)
+0.04
8
7
0.08 or less
−0.02
12.81 (
+0.04
)
9
8
0.10 or less
−0.02
16.00 (
+0.04
)
9
8
0.13 or less
−0.02
19.19 (
)
+0.03
11
10
0.15 or less
−0.03
22.36 (
+0.03
)
11
10
0.16 or less
−0.03
28.75 (
)
+0.06
13
12
0.20 or less
−0.02
35.11 (
+0.04
)
14
13
0.25 or less
−0.04
38.31 (
)
+0.08
15
14
0.27 or less
−0.02
41.50 (
)
+0.08
15
14
0.28 or less
−0.02
OD (Inch)
OD (mm)
OK
1/4ʺ
6.35
OK
3/8ʺ
9.52
OK
1/2ʺ
12.70
OK
5/8ʺ
15.88
OK
3/4ʺ
19.05
OK
7/8ʺ
22.22
OK
1-1/8ʺ
28.58
OK
1-3/8ʺ
34.92
OK
1-5/8ʺ
41.28
(Unit: mm)
Min. thickness
of coupling
0.50
0.60
0.70
0.80
0.80
0.82
1.00
1.20
1.26
1.35
Minimum wall thickness
(mm)
0.80
0.80
0.80
1.00
1.00
1.00
1.00
1.20
1.40
124-EN