F-GAS label
This product contains fluorinated greenhouse gases
• Chemical Name of Gas
• Global Warming Potential (GWP) of Gas
CAUTION
1. Stick the enclosed refrigerant label adjacent to the service ports for charging or recovering location and where
possible adjacent to existing nameplates or product information label.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the
included transparent protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained fluorinated greenhouse gas. Ensure that the fluorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained
fluorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
4. Only qualified service personnel are allowed to access and service this product.
5. Any handling of the fluorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EU) Regulation No. 517/2014 on certain fluorinated greenhouse gases and any
relevant local legislation.
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.
137-EN
1117101201-3 EN.indd 69
1117101201-3 EN.indd 69
R410A
2088 (ex.R410A ref.AR4)
– 69 –
Heat insulation for pipe
• Apply heat insulation of pipe separately at the liquid, gas, and balance sides.
• Be sure to use thermal insulator resistant up to 120°C or higher for pipes at the gas side.
Finishing after connecting pipes
• After piping connection work has been finished, cover the opening of the piping/wiring panel with the piping
cover, or fill silicon or putty into the space between the pipes.
• In case of drawing-out the pipes downward or sideward, also close the openings of the base plate and the side
plate.
• Under the opened condition, a problem may be caused due to the entering of water or dust.
When using the piping cover
Piping/wiring panel
Drawing-out sideward
Close the opening with the
pipe cover.
Drawing-out
frontward
Drawing-out
downward
¿ Pipe holding bracket
Attach pipe holding brackets following the table below.
Diameter of pipe (mm)
Interval
Ø15.9 - Ø19.1
2m
Ø22.2 - Ø41.3
3m
When not using the piping cover
Piping/wiring panel
Drawing-out sideward
Fill silicon or putty into the
periphery of the pipes.
Drawing-out
frontward
Drawing-out
downward
8/8/2559 BE 3:49 PM
8/8/2559 BE 3:49 PM
138-EN