8

Electric wiring

WARNING
The appliance shall be installed in accordance with national wiring regulations.
Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.
CAUTION
• Perform wiring of power supply complying with the rules and regulations of the local electric company.
• Do not connect 380V - 415V power to the terminal blocks for control cables (U1, U2, U3, U4, U5, U6, U7, U8);
otherwise, the unit may break down.
• Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the
coating of cables may melt and cause an accident.
• After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.
• Follow the same structure for both the control wiring and refrigerate piping.
• Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.
• For the wiring of power to indoor units and that between indoor and outdoor units, follow the instructions in the
installation manual of each indoor unit.
Power supply specifications
Do not bridge the power between outdoor units
through the equipped terminal blocks (L1, L2, L3, N)
139-EN
1117101201-3 EN.indd 70
1117101201-3 EN.indd 70
Power supply for
outdoor units
NO GOOD
– 70 –
¿ Power wiring selection
• Select the power supply cabling of each outdoor unit from the following specifications:
Cable 5-core, in conformance with design H07 RN-F or 60245 IEC 66.
• To decide nominal cross sectional area of conductor, refer to following table of Maximum Overcurrent Protection
(Amps).
Standard model
Power Supply
Model name
Phase and frequency
MMY-MAP0806*
MMY-MAP1006*
MMY-MAP1206*
MMY-MAP1406*
3N~50Hz
MMY-MAP1606*
MMY-MAP1806*
MMY-MAP2006*
MMY-MAP2206*
MMY-AP2416*
MMY-AP2616*
MMY-AP2816*
MMY-AP3016*
MMY-AP3216*
MMY-AP3416*
3N~50Hz
MMY-AP3616*
MMY-AP3816*
MMY-AP4016*
MMY-AP4216*
MMY-AP4416*
MMY-AP4616*
MMY-AP4816*
MMY-AP5016*
MMY-AP5216*
3N~50Hz
MMY-AP5416*
MMY-AP5616*
MMY-AP5816*
MMY-AP6016*
High efficiency model
Power Supply
Model name
Phase and frequency
MMY-AP2026*
3N~50Hz
MMY-AP2226*
MMY-AP3626*
MMY-AP3826*
MMY-AP4026*
3N~50Hz
MMY-AP4226*
MMY-AP4426*
MMY-AP5426*
MCA:Minimum Circuit Amps
MOCP:Maximum Overcurrent Protection (Amps)
MCA
MOCP
(A)
(A)
Nominal Voltage
20.5
25
21.5
25
26.1
32
31.0
40
380-400-415V
35.8
40
40.6
50
44.9
63
49.3
63
52.2
63
57.1
63
61.9
80
66.8
80
71.6
80
380-400-415V
76.4
100
80.7
100
85.1
100
89.8
100
94.2
125
98.6
125
102.6
125
107.4
125
112.2
125
116.5
160
380-400-415V
120.9
160
125.6
160
130.0
160
134.4
160
MCA
MOCP
(A)
(A)
Nominal Voltage
43.0
63
380-400-415V
47.6
63
78.3
100
83.2
100
88.1
100
380-400-415V
93.0
125
97.8
125
120.8
160
140-EN