Evaluating Screen Numbers - Siemens SIMATIC HMI OP3 Equipment Manual

Operator panel
Table of Contents

Advertisement

Process-Dependent Operator Guidance

11.3 Evaluating Screen Numbers

Application
The screen number area is located on the PLC. The OP3 writes the number of
the current screen to this area. If the PLC writes a screen number to the
screen number area, the screen is opened on the OP3. You can configure
operator guidance in this way.
Configuring
If the screen number area is to be used, it must be specified during
screen
configuration as the area pointer and created on the PLC. Figure 11-5 shows
number area
the construction of the screen number area.
Figure 11-5 Construction of the Screen Number Area on the PLC
The screen number area consists of two consecutive data words. The first
data word is used by the OP3 to store information about the display contents
(screen number and entry number).
If the PLC stores screen numbers and entry numbers in the second data word,
the display of a specific screen or a specific screen entry is initiated on
the OP3.
The hexadecimal value FFFF in the first or the second data word indicates
the message level; a value of 0 in the second data word indicates enabling of
OP3 operation.
Automatic change
0xFF is written to the screen number area when the OP3 jumps to message
to message level
level; on its return, the number of the last screen called is sent once more.
11-4
7..
1st word
Screen number
Screen number
2nd word
Bit 7 = 1: ID for special screen
..0
7..
..0
Entry number
Entry number
Operator Panel OP3