Installation

3 Installation

3.1 Installation Procedure

3
3
CAUTION
EQUIPMENT DAMAGE
If mains and control voltage are applied when installing
or removing options/accessories, it may damage the
equipment.
To avoid damage:
Remove mains and control voltage from the
soft starter before attaching or removing
options/accessories.
Installing the Modbus TCP Module:
1.
Remove control power and mains supply from
the soft starter.
2.
Fully pull out the top and bottom retaining clips
on the module (A).
3.
Line up the module with the communication port
slot (B).
4.
Push in the top and bottom retaining clips to
secure the module to the soft starter (C).
5.
Connect Ethernet port 1 or port 2 on the Modbus
TCP Module to the network.
6.
Apply control power to the soft starter.
A
Illustration 3.1 Installing the Modbus TCP Module
6
Modbus TCP Module
B
C
Danfoss A/S © 10/2017 All rights reserved.
Remove the module from the soft starter:
1.
Remove control power and mains supply from
the soft starter.
2.
Disconnect all external wiring from the module.
3.
Fully pull out the top and bottom retaining clips
on the module (A).
4.
Pull the module away from the soft starter.
A
Illustration 3.2 Removing the Modbus TCP Module
MG17N102