Device
Signal
No.
RWw10,
RWw12,
Link parameter
RWw14,
expansion setting/
RWw16,
Instruction code
RWw18
RWw11,
RWw13,
RWw15,
Write data
RWw17,
RWw19
Set the instruction code (refer to page 55) for execution of operation mode rewrite,
Pr. read/write, error reference, error clear, etc. The corresponding instruction is
executed in order of RWw2, 10, 12,14,16, 18 by switching on RYF after completion
of register setting, then, RXF switches on on completion of instruction execution.
Set HFFFF to disable an instruction by RWw10 to 19. (RWw2 is always executed.)
The first 8bits is link parameter expansion setting.
Example) When reading Pr. 300, instruction code is H0300.
Set the data specified by the instruction code of RWw10, 12, 14, 16, and 18. (when
required)
RWw10 and 11, 12 and 13, 14 and 15, 16 and 17, and 18 and 19 correspond each
other.
After setting this register corresponding to the instruction code of RWw10, 12, 14,
16, and 18, switch on RYF.
Set zero when the write code is not required.