4.3.1

Communication EEPROM write selection (Pr. 342)

When parameter write is performed from the communication option, write to RAM is enabled. Set when
frequent parameter changes are necessary.
Parameter
Number
Communication EEPROM write
342
selection
When changing the parameter values frequently, set "1" in Pr. 342 to write them to the RAM.
Performing frequent parameter write with "0 (initial value)" (EEPROM write) set in will shorten the life of
the EEPROM.
REMARKS
When "1" is set in Pr. 342 (write to RAM only), powering off the inverter will erase the changed parameter values.
Therefore, the parameter values available when power is switched on again are the values stored in EEPROM
previously.
Initial
Name
Value
Setting
Range
Parameter
0
communication
EEPROM and RAM.
0
Parameter
1
communication are written to the RAM.
INVERTER SETTING
Description
values
written
by
are
written
to
the
values
written
by
23