Mitsubishi Electric FR-A7NC Instruction Manual page 36

Plug-in option, cc-link communication function
Hide thumbs Also See for FR-A7NC:
Table of Contents

Advertisement

INVERTER SETTING
CAUTION
1.
When a communication line error has occurred, reset cannot be made from the network.
2.
The inverter is set to the external operation mode if it has been reset in network operation mode.
To resume the network operation, the inverter must be switched to the network operation mode again.
Set a value other than "0" in Pr. 340 to start in network operation mode. (Refer to page 17.)
3.
Communication continues during inverter reset. (The inverter can not be controlled for about 1s after
release of a reset command .)
(2) Error reset operation selection at inverter fault
When used with the communication option (FR-A7NC), an error reset command (RY1A) from network
can be made invalid in the external operation mode or PU operation mode.
Parameter
Number
Communication reset
349
selection
30
Initial
Name
Value
0
Setting
Range
Error reset (RY1A) is enabled independently of
0
operation mode
Error reset (RY1A) is enabled only in the network
1
operation mode
Function