Page 2
(indoors). The ambient temperature must be within 5 °C…55 °C. The flow sensor, however, may be installed in condensing environments. Maintenance and repair The flow sensor and the temperature sensors must not be separated from the calculator. Repairs require subsequent reverification in an accredited laboratory. Kamstrup A/S • 55121351_D2_GB_04.2015...
5.3 Position of calculator 1 General information Please read this guide carefully before installing the energy meter. In case of incorrect mounting, Kamstrup's guarantee obligations no longer apply. Note that the following installation conditions must be obeyed: - Pressure stage: PN16/PN25, see marking.
2.2 Coupling for direct sensor Slide the enclosed plastic coupling into place from the end of the sensor tube until you feel a click when the coupling has reached the first knurling. Kamstrup A/S • 55121351_D2_GB_04.2015...
Info codes 4 and 8 are set when the temperature falls below 0.00 °C or exceeds 155.00 °C. Info codes 4 and 8 are also set for short-circuited and disconnected sensors. Note: If Info = 4 or 8, the meter's energy calculation and volume accumulation stop. Kamstrup A/S • 55121351_D2_GB_04.2015...
In order to prevent cavitation, the operating pressure at MULTICAL® 302 must be min. 1 bar at q and min. 2 bar at q . This applies to temperatures up to approx. 80 °C. MULTICAL® 302 must not be exposed to pressure lower than the ambient pressure (vacuum). Kamstrup A/S • 55121351_D2_GB_04.2015...
The meter is most sensitive to air bubbles in the water when the plastic case points upwards. Therefore, this mounting position ought only to be used in installations with high operating pressure and automatic ventilation like e.g. direct connected district heating. Kamstrup A/S • 55121351_D2_GB_04.2015...
13). Icon for outlet meter 4.4 Humidity and condensation If MULTICAL® 302 is installed in moist 45° environments, it must be turned 45° compared to the pipe axis, as shown in the drawing to the left. Kamstrup A/S • 55121351_D2_GB_04.2015...
B and draw it around the cable C . Finally the cable binder is strapped around the flow cable again tying the cable to the flow sensor D . Kamstrup A/S • 55121351_D2_GB_04.2015...
However, INFO code 128 indicates that the battery voltage is too low. The battery cannot and must not be charged and must not be short-circuited. Used batteries must be handed in for approved destruction, e.g. to Kamstrup A/S. Kamstrup A/S • 55121351_D2_GB_04.2015...
If the meter has integrated wireless M-Bus, it is possible to select between Mode C1 or Mode T1 OMS. Mode C1 is used in connection with Kamstrup's reading systems and in general for drive-by meter reading. Mode T1 OMS is used in connection with OMS-based stationary networks.
(can only be changed with country code 6xx. Other country codes show 180 °C without the changing option) 11.0 Radio "ON" or "OFF" 3-11 12.0 End setup 3-12 After 4 minutes without activation of the button, the meter reverts to energy reading in the User loop. Kamstrup A/S • 55121351_D2_GB_04.2015...
When the transport mode has been cancelled, you only have access to the Setup loop if the installation seal is broken and the contact points behind the seal are short-circuited. Note: The option Setup has been deselected in certain country codes. Kamstrup A/S • 55121351_D2_GB_04.2015...
3. In return you receive a higher resolution. Example 5 MWh with 3 decimals (B=4) In principle, this is the same resolution as in example 3, but energy is now counted in MWh. Kamstrup A/S • 55121351_D2_GB_04.2015...
Page 15
Current inlet temperature. Current information code (contact your utility if the value differs from "0"). Current outlet temperature. Current heat power. Current differential Current water flow. temperature. DDD=210 Furthermore, see interactive user's guides at www.kamstrup.com...