Configuration of detector type

The point detectors FDOOT241-A9-Ex and OOH740-A9-Ex can be set to the
existing detector type using parameter set resistors.
Procedure:
 Detector bases FDB20x or FDB22x are installed.
1. Install a point detector FDOOT241-A9-Ex or OOH740-A9-Ex directly in the new
detector base as a replacement for a point detector DO1101A-Ex.
2. If the point detector FDOOT241-A9-Ex or OOH740-A9-Ex is intended to
replace a heat detector: Also install a standard resistor to set another
parameter set.
-
Determine the resistance required using the table below.
-
Install the resistor as shown in the diagram.
 The point detector FDOOT241-A9-Ex or OOH740-A9-Ex is installed and
configured.
Installing the parameter set resistor R in the detector base
-
-
-
+
+
+
R
Values for the parameter set resistor R (≥ 200 mW)
R
Parameter set
Sensitive (when replacing a point detector DO1101A-Ex)
18 kΩ
A1R (when replacing a point detector DT1101A-Ex)
10 kΩ
BR (when replacing a point detector DT1102A-Ex)
Undertaking modernization
Step 1: Detector modernization
A6V10443621_a_en_--
4
17
2014-09-01