22-Series I/O Module

20-750-2262C-2R (24 Volts DC)
20-750-2263C-1R2T (24 Volts DC)
20-750-2262D-2R (120 Volts AC)
Table 59 - Input Mode Jumpers
Jumper
Voltage Mode
Position
Table 60 - TB1 Terminal Designations
Terminal Name
Sh
Shield
Sh
Ptc–
Motor PTC (–)
Ptc+
Motor PTC (+)
Ao0–
Analog Out 0 (–)
Ao0+
Analog Out 0 (+)
Sh
Ao1–
Analog Out 1 (–)
Sh
PTC–
PTC+
Ao1+
Analog Out 1 (+)
Ao0–
Ao0+
Ao1–
–10V
–10 Volt Reference
Ao1+
–10V
10VC
10VC
10 Volt Common
+10V
Ai0–
Ai0+
+10V
+10 Volt Reference
Ai1–
Ai1+
24VC
Ai0–
Analog Input 0 (–)
+24V
DiC
Di0
Ai0+
Analog Input 0 (+)
Di1
Di2
Di3
Ai1–
Analog Input 1 (–)
Di4
Di5
Ai1+
Analog Input 1 (+)
24VC
24 Volt Common
+24V
+24 Volt DC
Di C
Digital Input Common Common for Digital Inputs 0...5
Di 0
Digital Input 0
Di 1
Digital Input 1
Di 2
Digital Input 2
Di 3
Digital Input 3
Di 4
Digital Input 4
Di 5
Digital Input 5
(1) Digital Inputs are either 24 Volts DC (2262C) or 115 Volts AC (2262D) based on module catalog number. Ensure applied voltage is
correct for I/O module.
(2) See HW Input PTC on
page 258
for PTC data.
(3) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode
immunity.
(4) For CE compliance use shielded cable. Cable length should not exceed 30 m (98 ft).
(5) I/O Module parameters will also have a Port designation.
Rockwell Automation Publication 750-IN001O-EN-P - October 2014
Current Mode
Ai1
Ai0
Description
Terminating point for wire shields when an EMC plate
or conduit box is not installed.
Motor protection device (Positive Temperature
(2)
Coefficient).
Bipolar, ±10V, 11 bit & sign, 2 k ohm minimum load.
4-20 mA, 11 bit & sign, 400 ohm maximum load.
2k ohm minimum.
For (–) and (+) 10 Volt references.
2k ohm minimum.
(3)
Isolated
, bipolar, differential, 11 bit & sign.
Voltage Mode: ±10V @ 88k ohm input impedance.
Current Mode: 0-20 mA @ 93 ohm input impedance.
Drive supplied logic input power.
200 mA max. per I/O module
600 mA max per drive
(1)
24V DC (30V DC Max.) - Opto isolated
(1)
High State: 20...24V DC 11.2 mA DC
Low State: 0...5V DC
(1)
120V AC (132V AC Max.) 50/60 Hz
(1)
High State: 100...132V AC
(1)
Low State: 0...30V AC
(1)
I/O Wiring
Chapter 5
Ai1
Ai0
Related
(5)
Param
40
on Port X
75
on Port X
85
on Port X
50, 70
on Port X
60, 70
on Port X
1
on Port X
(4)
- Opto isolated
255