4.1

Technical data

4.1.1

Interfaces

Bus In (system bus)
Application
Number
Connection
Connection cable
Cable length
Bus Out1 and Bus Out2 (system bus)
Application
Number
Connection
Connection cable
Cable length
4.1.2

Electrical data

Voltage supply
Connection
Voltage input
Residual ripple
Current consumption
Power consumption
Conductor cross section (voltage supply)
Wire or strand without ferrule
Strand with ferrule
2 x strand with twin ferrule
with plastic collar
Stripping length
Electrical safety
Electromagnetic compatibility
Interference emission
Interference immunity
For connection of a base unit, a router module or a multifunction
panel
1
At the front, RJ45 socket
Network cable (patch cable or crossover cable), at least CAT5 (S/
FTP)
Up to 100 m
For connection of further router modules or a multifunction panel
2
At the front, RJ45 socket
Network cable (patch or crossover cable), at least CAT5 (S/FTP)
Up to 100 m
At the front (removable 2-pole terminal strip with Push-In technol-
ogy)
DC 24 V +25/-20 % SELV
5 %
100 mA (at DC 19.2 V)
Current consumption of lined-up modules also has to be considered
(see „Hardware configuration" in the setup program)!
2 W
2
Min. 1.5 mm
, max. 2.5 mm
2
Min. 1.5 mm
, max. 2.5 mm
2
1.5 mm
10 mm
Acc. to DIN EN 61010-1
Overvoltage category III, pollution degree 2
Acc. to EN 61326-1
Class A – only for industrial use –
Industrial requirements

4 Appendix

2
2