Finishing

A. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specified. Framing or finishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
Clearance to combustible material under the insert is 3/4
in. (19 mm). Clearance from top of fireplace opening for
combustibles extending 12 Inches max. is 12 Inches.
• Use leveling legs to raise insert minimum 3/4 in. (19 mm)
above combustible material or outer wrap of factory built
firebox.
• If 3/4 in. gap is not achievable, the appliance may be
placed directly on a non-metallic 1/2 in. non-combustible
board. See Figure 10.2 for minimum required coverage
area.
Combustible facings must not extend behind the insert
surround. For non-combustible material specifications
refer to section 1.E.
EXISTING NON-COMBUSTIBLE FACING
Figure 10.1 Mantel Clearance
Heat & Glo • ESCAPE-35-IFT, ESCAPE-30-IFT Installation Manual • 2550-980 Rev. B • 6/18
24
Figure 10.2 Alternate Minimum Non-Combustible Board Coverage
12 IN.
MAX.
12 IN. MIN.
SIZE
DEPTH (D)
30 in.
14
35 in.
15
NON-COMBUSTIBLE
D
AREA
Requirement
WIDTH (W)
21
25
W