Table 10 - Natural Gas (Ft 3 /Hr) Maximum Piping Capacities; Table 11 - Propane (Kbtu/Hr) Maximum Piping Capacities; Table 12 - Gas Inlet Pressure; Table 13 - Manifold Pressure - AAON V3-A Installation, Operation & Maintenance Instructions Manual

V3 series vertical indoor air handling units
Table of Contents

Advertisement

Table 10 - Natural Gas (ft
Specific Gravity = 0.6, Supply Pressure ≤ 0.5 psi, Pressure Drop = 0.5"wc
Pipe Size
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"

Table 11 - Propane (kBtu/hr) Maximum Piping Capacities

Specific Gravity = 1.52, Supply Pressure = 11"wc., Pressure Drop, 0.5"wc
Pipe Size
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
After verifying gas inlet pressure and
manifold pressure the service technician must
time the gas flow rate through the gas meter
with a stopwatch to verify the gas input rate.

Table 12 - Gas Inlet Pressure

Gas Inlet
Pressures ("wc)
Minimum
Maximum
Unit nameplate input rate value has been
calculated at the altitude where the unit was
shipped. Above 2,000 ft the input rate is
adjusted 4% for every 1,000 ft.
A factory installed pressure tap on the outlet
end of the gas valve can be used to verify the
manifold pressure.
20 ft
50 ft.
120
73
250
151
465
285
950
580
1460
900
2750
1680
4350
2650
20 ft
50 ft.
189
114
393
237
732
448
1496
913
2299
1417
4331
2646
Natural
Propane
Gas
Gas (LP)
6.0"wc
11.0"wc
10.5"wc
13.0"wc
3
/hr) Maximum Piping Capacities
Length of Pipe
100 ft.
50
103
195
400
620
1150
1850
Length of Pipe
100 ft.
78
162
307
630
976
1811

Table 13 - Manifold Pressure

Unit Size (V3-)
A
B
C
Do not use gas piping smaller than unit gas
connections. Natural gas pipe runs longer
than 20 feet and propane gas pipe runs longer
than 50 feet may require a larger supply pipe
than the unit connection size. Some utility
companies may also require pipe sizes larger
than the minimum sizes listed.
150 ft.
200 ft.
40
35
84
72
160
135
325
280
500
430
950
800
1500
1280
150 ft.
200 ft.
63
55
132
112
252
213
511
440
787
675
1496
1260
Natural
Propane
Gas
Gas (LP)
10.5"wc
3.5"wc
10.0"wc

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

V3-bV3-cV3-eV3-d

Table of Contents