Technical specifications
Article number
Digital inputs
Number of digital inputs
Digital inputs, parameterizable
Type
Pulse extension
Time stamping
Time stamp (with precision of 1 ms)
Edge evaluation
Signal change flutter
Flutter observation window
Input voltage
● Type of input voltage
● Rated value (DC)
Input current
for 10 k switched contact
for unswitched contact
for NAMUR encoders
Input delay (for rated value of input voltage)
● tolerated changeover time for changeover
for NAMUR inputs
Cable length
● shielded, max.
● unshielded, max.
Encoder
Connectable encoders
● NAMUR encoder/changeover contact
● Single contact / changeover contact
● Single contact / changeover contact
● 2-wire sensor
32
–
for signal "0"
–
for signal "1"
–
for signal "0", max. (permissible
quiescent current)
–
for signal "1"
–
for signal "0"
–
for signal "1"
contacts
–
at "0" to "1", max.
–
at "1" to "0", max.
according to EN 60947
unconnected
connected with 10 kΩ
6DL1131-6TH00-0PH1
16
Yes
NAMUR
Yes; 0.5 s, 1 s, 2 s
Yes
No
Yes; rising edge, falling edge, edge change
Yes; 2 to 32 signal changes
Yes; 0.5 s, 1 s to 100 s in 1-s steps
DC
8.2 V
0.35 to 1.2 mA
2.1 ... 6.4 mA
0.5 mA
typ. 8 mA
0.35 to 1.2 mA
2.1 ... 6.4 mA
300 ms
17 ms
25 ms
600 m
200 m
Yes
Yes
Yes
Yes; Acc. to NAMUR
Digital Input Module DI 16xNAMUR HA (6DL1131-6TH00-0PH1)