ON-OFF
Press the [On/Off] button to turn the thermostat ON or OFF.
Set point
Press the [+] or [-] buttons once to view the set point temperature.
Press again to adjust the set point.
Modes
Press the [Mode] button to switch between modes:
"Cool"..................... Cooling
"Heat"..................... Heating
"Cool" & "Heat"......... Auto mode
"Fan"...................... Fan only
Notes:
1. During demand for cooling or heating, the active mode will flash.
2. Heat and Auto modes are not available in cool only configuration.
Fan speeds (for 3 speed configuration only)
Press the [Fan] button to switch between fan speeds:
"Lo"........................ Low speed
"Me"........................Medium speed
"Hi".........................High speed
"Auto"......................Auto speed
Note: In Auto speed, the active fan speed will flash.
Auto fan (fan on demand)
For 3 speed configuration:
Press and hold the [Fan] button (5 sec.) to turn Auto fan ON or OFF.
When ON, the fan will work on demand for cooling or heating,
When OFF, the fan will work continuously.
Note: Auto fan cannot be selected in Fan only mode.
For 1 speed configuration:
Press the [Fan] button to turn Auto fan ON or OFF.
When ON, the fan will work on demand for cooling or heating,
When OFF, the fan will work continuously.
Note: Auto fan cannot be selected in Fan only mode.
Note: in Oil/Gas systems, with Auto Fan ON, the fan will never be activated.
ETN24-SUPER-SH-F
Owner's manual & Technnician Settings
Cool
Pg. 1
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
Cool
Heat
Heat
Cool
Heat
Me
Lo
Low
Medium
speed
speed
File: ETN24-SUPER-SH-F_operating manual.vsd
o
F
Aux
Fan
Auto
Fan only
mode
Hi
Hi
Me
Lo
High
Auto
speed
speed
Fan
Auto Fan
Auto fan
Auto fan
OFF
ON

Advertisement

loading
Need help?

Need help?

Do you have a question about the ETN24-SUPER-SH-F and is the answer not in the manual?

Questions and answers

Summary of Contents for meitav-tec ETN24-SUPER-SH-F

  • Page 1: Operating Instructions

    Note: Auto fan cannot be selected in Fan only mode. Note: in Oil/Gas systems, with Auto Fan ON, the fan will never be activated. File: ETN24-SUPER-SH-F_operating manual.vsd Pg. 1 Tel: (856) 2882882 ETN24-SUPER-SH-F Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technnician Settings support@meitavtec.com...
  • Page 2: Installation

    Installation The ETN24-SUPER-SH-F is designed for wall mounting in the room to be controlled. It should be located where the occupant can easily read the LCD display and use the controls. If the built in temperature sensor is being used to measure room temperature, the module should be placed where the temperature is representative of the general room conditions.
  • Page 3 If two heaters are being used (1 fan speed config. Only) connect them to W1 and W2 (1 and 2 stage heat). Pg. 3 Tel: (856) 2882882 ETN24-SUPER-SH-F Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technician Settings support@meitavtec.com...
  • Page 4 S2.6 – OFF Economy Note: Economy mode set points are set by technician – refer to technician settings. 1 2 3 4 5 6 Outputs OFF Pg. 4 Tel: (856) 2882882 ETN24-SUPER-SH-F Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technnician Settings support@meitavtec.com...
  • Page 5 AUTO FAN ON - The fan will work on demand for heating. heater Without AUTO FAN - The Fan will work continuously. Important: Switches 4 and 6 are not in use and must remain OFF. Pg. 5 Tel: (856) 2882882 ETN24-SUPER-SH-F Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technnician Settings support@meitavtec.com...
  • Page 6: Technician Settings

    Use the [+] and [-] buttons to adjust the dead zone between cooling and heating. Range: 2...10°F, Default 2°F. Press the [Mode] button again to return to normal display. Dead zone Pg. 6 Tel: (856) 2882882 ETN24-SUPER-SH-F Tel: +972-3-9626462 Fax: +972-3-9626620 Owner’s manual & Technnician Settings support@meitavtec.com...