Rosemount 2051cf series flowmeter transmitter
with profibus pa.
pressure transmitter with profibus pa (21 pages)
Summary of Contents for Rosemount 3095MF Series
Page 1
® OUNDATION ™ Transmitter with HART or F Fieldbus Protocol Rosemount 3095MF Series Flowmeter Transmitter Start Step 1: Mount the Transmitter Step 2: Transmitter Installation Step 3: Software Installation Step 4: Connect the Wiring and Power Up (HART or Fieldbus)
Page 4
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 1: M OUNT THE RANSMITTER Liquid Flow Applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward.
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 2: T RANSMITTER NSTALLATION Consider Housing Rotation To improve field access or to better view the optional LCD display: 1. Loosen the housing rotation set screw. 2. Rotate the housing clockwise to the desired position – up to 180° from its original position.
Page 6
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 CONTINUED 3. Set the Failure Mode Alarm (HART devices), which is located on the front of the electronics board inside the electronics housing cover. The Alarm Jumper position determines if the output is driven high or low when a failure is detected. The transmitter operates normally if the jumpers are not installed and the Alarm default fail is HI.
Page 7
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 CONTINUED • Installing a Shielded 3095 RTD Cable (See Figure 4) Note: Shielded cable is intended for use in a conduit. a.Fully engage the black cable connector to the 3095 RTD Connector.
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 CONTINUED Bolting Considerations If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters.
Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring that is designed for its specific flange adapter, as shown below. Rosemount 3051S / 3051 / 2051 / 3095 Flange Adapter O-ring...
CD-ROM disk 2 into the drive and run the EAUpgrade.exe from Windows 98, NT, 2000, or XP. To properly install, the program will first uninstall Engineering Assistant from the computer. (Upgrades also are available at www.rosemount.com.) b.Remove the installation disk and reboot the computer to complete installation.
Page 11
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 CONTINUED Installing the HART Modem After installing the 3095 Engineering Assistant, the HART modem configuration window automatically appears when the 3095 Engineering Assistant is opened. If this window is canceled, the HART modem may be installed manually with the following procedure.
Page 12
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 4: C 4: C (HART) (HART) ONNECT ONNECT IRING AND IRING AND OWER OWER Use the following steps to wire the transmitter: 1. Remove the housing cover on the side marked FIELD TERMINALS.
Page 13
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 4: C ONNECT IRING AND OWER IELDBUS Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field Terminals.” Terminals are not polarity sensitive. 2. Connect the signal leads to the terminals labeled “Fieldbus Wiring”.
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 5: C (HART) ONFIGURE THE RANSMITTER Setting the Loop to Manual Set the process application loop to manual when preparing to send or request data that would disrupt the loop or change the output of the transmitter. A prompt will appear reminding the user to set the loop to manual when necessary.
Page 15
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 Function/Variable Fast Key Sequence DP Sens Trim 1, 2, 2, 1, 1 DP Snsr Range 1, 3, 5, 1 DP URV DP units 1, 3, 2, 1 Date 1, 3, 4, 4...
Page 16
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 5: C ONFIGURE THE RANSMITTER IELDBUS Each F fieldbus host or configuration tool has a different way of displaying and OUNDATION performing configurations. Some use Device Descriptions (DD) or DD methods for configuration and to display data consistently across platforms.
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 6: T RIM THE RANSMITTER NOTE Transmitters are shipped from Emerson Process Management fully calibrated and configured for the application when C2 Option is ordered. Without C2 Option, configuration will be by the factory default (span = upper range limit for F fieldbus transmitters).
European Directive Information The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office. ATEX Directive (94/9/EC) Emerson Process Management complies with the ATEX Directive.
Page 19
II/Class III, Division 1, Groups E, F, and G. CSA enclosure Type 4X suitable for indoor and outdoor hazardous locations. Provides nonincendive RTD connection for Class I, Division 2, Groups A, B, C, and D.Factory Sealed. Install in accordance with Rosemount Drawing 03095-1024. Approved for Class I, Division 2, Groups A, B, C, and D.
Page 20
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 G ATEX Type n Certificate Number: BAS98ATEX3360X II 3 G Ex nL IIC T5 (T = –45 °C to 40 °C) Ex nL IIC T4 (T = –45 °C to 70 °C)
Page 21
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 Table 7. RTD Terminals Entity Parameters = 30Vdc = 19 mAdc = 140 mW The capacitance and either the Inductance or the Inductance to Resistance Ratio (L/R) of the load connected to the 4-pin connector must not exceed the following values:...
Page 22
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 China (NEPSI) Certifications China Intrinsic Safety Ex ia IIC T4 Special conditions for safe use (x): 1. 3095 Series transmitter with temperature sensor have not been certified. 2. The temperature of process medium should be less than 121 °C.
Page 23
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 11.When installation, use and maintenance transmitter, observe the following standards GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres”...
Page 24
European Directive Information The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office. ATEX Directive (94/9/EC) Emerson Process Management complies with the ATEX Directive.
Page 25
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D. When installed in accordance with Rosemount Drawing 03095-1021. Temperature Code T3C. W FISCO Field Device. Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D. When installed in accordance with Rosemount Drawing 03095-1021. Temperature Code T3C. European Certifications...
Page 26
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 Table 9. Temperature Sensor Connection Parameters = 30V = 19 mA = 140 mW Table 10. Connection Parameters for Temperature Sensor Terminals = 0.066 F Gas Group IIC = 0.560 F Gas Group IIB = 1.82 F...
Page 27
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 ATEX Dust Certificate Number: KEMA02ATEX2321 II 1 D T90°C (-50°C T 80°C) Vmax = 55 Vdc Imax = 23 mA IP66 1180 IECEx Certifications (Fieldbus) 4/Y IECEx Intrinsic Safety Certificate Number: IECEx BAS05.0023X...
Page 28
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009 IECEx Flameproof Certificate Number: IECEx KEM 06.0018 Zone 0/1 Ex d IIC T6 (-20°C T 65°C) Zone 0/1 Ex d IIC T5 (-20°C T 80°C)
Page 29
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009...
Page 30
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009...
Page 31
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009...
Page 32
Quick Installation Guide 00825-0100-4716, Rev DA Rosemount 3095 MultiVariable October 2009...
Need help?
Do you have a question about the 3095MF Series and is the answer not in the manual?
Questions and answers