Page 1
For the operator ROTEX HPSU compact Instruction manual Solar tank with integrated interior heat pump unit For the types HPSU compact 304 HPSU compact 308 HPSU compact 508 HPSU compact 516 Output 09/2013...
(Drain Back) installation and operating instructions. Only applicable for the pressurised system – With connection of a ROTEX Solaris solar system; the asso- ciated installation and operating instructions. Valid/available only if a room regulator is connected – With connection of a ROTEX HP convectors; the associated Valid/available only if a mixer module is connected installation and operating instructions.
Safety 1.4 Intended use The ROTEX HPSU compact may only be used for preparation of warm water, as a room heating system, and depending on its design, as a room cooling system. Any other use outside the intended use is considered as improper. The operator alone shall bear responsibility for any resulting damage.
The storage tank on the ROTEX HPSU compact is built in such a storage tank, a high hot water output is achieved even if water is way to enable the heat pump system to be combined with a drawn off over a long period of time.
In the integrated storage tank of the ROTEX HPSU compact, the solar heat gen- erated in this way is transferred into the heating and hot water circuit.
Product description 2.2.2 Equipment external and internal structure HPSU compact 304/308 DB Fig. 2-2 Structure and constituents HPSU compact 304/308 DB (External appearance and internal structure) Designations of key see tab. 2-1 BA ROTEX HPSU compact 4 - 09/2013...
Product description 2.2.4 Equipment external and internal structure HPSU compact 508/516 DB Fig. 2-4 Structure and constituents HPSU compact 508/516 DB (External appearance and internal structure) Designations of key see tab. 2-1 BA ROTEX HPSU compact 4 - 09/2013...
Shown on type 508 Heat exchanger (stainless steel) for (1/4"), pressurised solar storage tank charging HPSU compact 516: CuT, Ø 9.5 mm (3/8") Tab. 2-1 Legend from fig 2-2 to fig 2-5 BA ROTEX HPSU compact 4 - 09/2013...
All function settings for the ROTEX HPSU compact and the op- tional RoCon equipment connected via the data bus are carried out with the operating elements of the integrated operating part RoCon B1 and displayed in clear text display on a coloured backlit display.
Independent of the setting of the rotary switch, the White: Standard lighting, normal operational display. ROTEX HPSU compact operates in accordance with Red: Fault status, depending on the type of fault, the the operating mode set in the switch position "Oper-...
Independent of the setting of the rotary switch, the in such a way that the frequently required setting facilities are ac- ROTEX HPSU compact operates in accordance with cessible quickly and directly at the main function level (selection the operating mode set in the switch position "Oper-...
In this rotary switch position, the rotary switch can be used to call inadvertent actuation (see fig. 3-4). up all the system temperatures, the type of ROTEX HPSU Unlocking can be carried out in the same way. compact, various software information and the operating sta- tuses of all system components, one after the other.
Page 15
Actual volume flow (flow rate) in the heating The permissible range of water pressure during operation de- system pends on the ROTEX HPSU compact and the heating system. Actual inflow temperature of heating facilities (t The set values and threshold values must only be changed by the Actual return flow temperature of heating facilities heating technician.
All controllers integrated into the RoCon-system via the CAN bus are also switched at a higher level to the operating mode In this mode, the ROTEX HPSU compact is shifted to the stand- "Summer". by mode. The frost-protection function remains in place. In order...
– [T-Reduced]: Set value for operating mode [Reducing] or set back by a permanent timer programme. – [T-Absence]: Set value for temporary heating / cooling programmes ("Away" and "Vacation"). Settings are displayed. ● Set the temperature. BA ROTEX HPSU compact 4 - 09/2013...
Entire week 06:00 -> 22:00 (Monday to Sunday) --:-- -> --:-- --:-- -> --:-- See HC Program 1 See HC Program 1 HC Program 2 Tab. 3-6 Menu structure heating circuit timer programme BA ROTEX HPSU compact 4 - 09/2013...
Page 19
, in the parameter [T-Absence]. "Set Temp Night" – The hot water generation is not affected. – The time programme runs for the set time period after acti- vation. BA ROTEX HPSU compact 4 - 09/2013...
RoCon M1). the basic settings for the Control RoCon HP and the system con- figurations for the installation environment of the ROTEX HPSU compacts, the direct heating circuit, the hot water generation and any optionally connected components.
● Confirm the changes with a brief push of the rotary switch. The local control element acts as the remote control for The manual mode serves to regulate the ROTEX HPSU compact the external equipment. manually to a specific flow temperature. The manual mode To end terminal mode and restore operation of the assigned should only be used for diagnostic purposes.
– Radiator and system 70: 1.4 to 1.6. – Underfloor heating system: 0.5 to 0.9. Access Rights Setup Expert Keylock Function Access Rights Code Reset Time Access Rights Access Rights Fig. 3-12 Entering the access code BA ROTEX HPSU compact 4 - 09/2013...
More detailed explanations and possible setting values for this function can be seen in chapter 6.2. External temperature Flow temperature Room temperature set value Fig. 3-14 Heat curves More detailed explanations and possible setting values for this function can be seen in chapter 6.2. BA ROTEX HPSU compact 4 - 09/2013...
3.6.5 Legionella protection If the "Weather-controlled flow temperature regulation" is active, The ROTEX HPSU compact itself does not need this function the flow temperature is determined automatically in because of the small volume of the internal drinking water heat accordance with the set heating curve depending on the outside exchanger.
Control RoCon HP can be connected to the Internet. This means of internal switching relays and sensors. that the ROTEX HPSU compact can be controlled remotely via mobile phone (using an App). ● Place the rotary switch in the "Configuration"...
4.1 Initial start-up and adjust where necessary (max. 3 bar). The ROTEX HPSU compact may be commissioned only by 6. Carry out a visual inspection for leaks on all joints internally. authorised and trained heating experts.
– the system or parts of the system are being dismantled and ● Dismount the safety overflow from the overflow reassembled in another location. connection (fig. 2-2 to fig. 2-5, pos. 23) of the ROTEX HPSU compact. The ROTEX HPSU compact is designed to be environmentally ●...
Page 28
The materials used that are suitable for recycling can be sorted into individual types. ROTEX has complied with the standards for environ- mentally-friendly disposal as a result of the environ- mentally-friendly design of the HPSU compact. Proper disposal in compliance with the respective national ...
On: The button block can be activated using the rotary switch (see chapter 3.1). Access Rights Entering access code. Setting character by character like a combination lock 0 - 9 0000 (see chapter 3.6.1). Tab. 6-1 Parameter in rotary switch setting "Configuration", level "Setup" BA ROTEX HPSU compact 4 - 09/2013...
+1 K. Insulation Setting the insulation standard of the building. This affects the way the heating curve and Normal the heating times automatically adapt to the outside temperature. Normal Good Very Good BA ROTEX HPSU compact 4 - 09/2013...
Page 31
This parameter can be used to adapt the room sensor in cooling mode -5 - 5°C 0 °C (Condition: Operating mode cooling). Tab. 6-3 Parameter in rotary switch setting "Configuration", level "HC Configuration" BA ROTEX HPSU compact 4 - 09/2013...
The internal heating circuit regulates according to the second parameterised timer programme [HC Program 2] with the individual day room temperatures set. The hot water generation takes place according to [DHW Program 2]. Tab. 6-6 Parameter in rotary switch setting "Operating Mode" BA ROTEX HPSU compact 4 - 09/2013...
Set value of the hot water temperature in °C that applies to the third switching cycle of the timer 10 - 70°C 48 °C 1 °C programmes [Automatic 1] and [Automatic 2]. Tab. 6-9 Parameter in rotary switch setting "DHW Set Temp" BA ROTEX HPSU compact 4 - 09/2013...
Activation switches to the HPSU compact with the bus ID X. Mix Valve #X Activation switches to the mixer module with the bus ID X (see section 6.12.1, parameter [HC Assignment]). Tab. 6-11 Parameter in rotary switch setting "Remote Param" BA ROTEX HPSU compact 4 - 09/2013...
Timeprog Reset Resets all permanent time programmes to factory setting (see tab. 3-7). Return This parameter is used only to exit the special level. Tab. 6-13 Parameter in the level "Sonderfunktion" BA ROTEX HPSU compact 4 - 09/2013...
On: The button block can be activated using the rotary switch (see chapter 3.1). Access Rights Entering access code. Setting character by character like a combination lock 0 - 9 0000 (see chapter 3.6.1). Tab. 6-14 Parameter in rotary switch setting "Configuration" level "Setup" BA ROTEX HPSU compact 4 - 09/2013...
1 °C Only if the solar system ROTEX is connected and parameterised: Room temperature, above which heat energy from the connected ROTEX solar system is made available at a heat demand. If the room temperature at the room temperature controller is greater than the value set here + 0.5 K, then the demand of the heat circuit is suppressed.
Page 38
In the individual menu levels, on the other hand, we show the fil- tered measured values relevant for the Controller. Sensor 1: Mixer circuit flow temperature sensor Sensor 2: Outside temperature sensor Tab. 6-15 Parameter in rotary switch setting "Configuration", level "Mixer Config" BA ROTEX HPSU compact 4 - 09/2013...
2. Close the ball cock heating circuit (fig. 7-3, pos. 3). ● If a ROTEX solar system of the type Drain Back 3. Disconnect the electrical plug connection on the 3-way connected and in operation, switch it off and empty the solar switching valve (3UV1) (fig.
Displays an active fault message (heat pump fault) 8.1.3 Solving failures Troubleshooting the electrical, coolant and hydraulic systems of the ROTEX HPSU compact may be per- formed only by authorised and trained heating experts. BA ROTEX HPSU compact 4 - 09/2013...
Operating data are not ● Restart system (mains voltage). Operating system of control unit crashed. updated ● Have the system checked by a ROTEX heating technician. Room heating standby switched off (e.g. time ● Check the operating mode setting. program is in the economy phase, outside tem- ●...
Page 45
Faults and malfunctions Malfunction Possible cause Possible solution ● Have the system checked by a ROTEX heating DIP switch configured incorrectly technician. Hot water supply switched off (e.g. time pro- ● Check the operating mode setting. gram is in the economy phase, parameters for ●...
● Bleed the entire water circuit. ● Check the HPSU compact, its components and Noises caused by vibrations. covers to ensure they are fastened correctly. ● Have the system checked by a ROTEX heating Bearings damage in the circulation pump. technician. Circulation pump is being excessively noisy ●...
Page 47
– With installed backup heater: STB in backup heater (BUH) > 65 °C in HPSU compact > 65 °C has triggered. IG main board 9007 PCB A1P HPSU compact Malfunction message. Contact ROTEX heating technician. defective No heat consumption at underfloor heat exchanger Refrigerant Refrigerant temperature 9008 ●...
Page 48
There is too little or no refrigerant left in the system. Check system 9038 Refrigerant leak Refrigerant loss for leaks, repair and refill. Under/ over 9039 Main circuit without power Malfunction message. Contact ROTEX heating technician. voltage 9040 Screed function Screed function active No fault. 9041...
The suitable flow temperature is calculated from the measured value for the external temperature and temperature regulation a defined heating curve; this temperature serves as the target value for temperature control in the heating unit. BA ROTEX HPSU compact 4 - 09/2013...
[T-DHW Setpoint 2]: ____ °C [T-DHW Setpoint 3]: ____ °C setting Time period Monday Tuesday Wednesday Thursday Friday Saturday Sunday Monday Tuesday Wednesday Thursday Friday Saturday Sunday Tab. 10-2 Individual settings in the hot water timer programmes BA ROTEX HPSU compact 4 - 09/2013...
Rotary switch Parameter Parameter Old value New value Date Comments setting level Tab. 10-4 Individual parameter modifications 10.1.3 Databus addresses HPSU compact-appliance Databus addresses Comments Tab. 10-5 Databus addresses in the HPSU compact-system BA ROTEX HPSU compact 4 - 09/2013...