4-2
Troubleshooting
Fault Indication
Condition
Drive is indicating a fault.
The integral LED display provides visual
notification of a fault condition by displaying the
following.
• Flashing fault number
• Flashing fault indicator
Press the Up Arrow key to regain control of the
display.
Manually Clearing Faults
Step
1. Address the condition that caused the fault.
The cause must be corrected before the fault can be cleared.
See
Table
2. After corrective action has been taken, clear the fault by one of these
methods.
• Press and hold the Up Arrow key for three seconds.
• Cycle drive power.
• Set
A100
• Cycle digital input if
"Clear Fault".
Automatically Clearing Faults
Option / Step
Clear a Type 1 fault and restart the drive.
1. Set
A092
2. Set
A093
Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault
without restarting the drive.
1. Set
A092
2. Set
A093
Auto Restart (Reset/Run)
The Auto Restart feature provides the ability for the drive to
automatically perform a fault reset followed by a start attempt without
user or application intervention. This allows remote or "unattended"
operation. Only certain faults are allowed to be reset. Certain faults
(Type 2) that indicate possible drive component malfunction are not
resettable. Fault types are listed in
descriptions.
Caution should be used when enabling this feature, since the drive will
attempt to issue its own start command based on user selected
programming.
4.B.
[Fault Clear] to "1" or "2".
A051-A054
[Digital Inx Sel] is set to option 7
[Auto Rstrt Tries] to a value other than "0".
[Auto Rstrt Delay] to a value other than "0".
[Auto Rstrt Tries] to a value other than "0".
[Auto Rstrt Delay] to "0".
Display
RUN
REV
FAULT
Table
4.A. Refer to
Key(s)
Table 4.B
for fault