String Protection Fuses; Sizing Of Fuses - ABB PVS-100 Product Manual

100 to 120 kw
Hide thumbs Also See for PVS-100:
Table of Contents

Advertisement

S
tring protection fuses
S
izing of fuses
CH1
CH2
1A
1B 1C
1D
2A
2B 2C
CH3
CH4
3A
3B 3C
3D
4A
4B 4C
CH5
CH6
5A
5B 5C
5D
6A
6B 6C
The correct sizing of the
wiring box model) string fuses to be used to protect from "return currents" is
very important because it can considerably limit the risk of fire and damage
to the PV generator.
A "return current" can be generated in the event of a fault and relevant
short-circuit at the ends of one or more PV modules of the system; this
condition can cause all the current supplied by the strings not involved in
the fault, but connected to the same input channel, to pass through the
faulty string.
For input connectors marked with "A" and "D" you must directly connect
the individual strings coming into the inverter (do not make field
switchboards for parallel strings). This is because the positive side
2D
and negative side
take strings in parallel (array).
This operation could damage the fuses and consequently could cause
malfunctioning of the inverter.
4D
The connection in parallel of the strings (array composition) could be
made upstream of the input connectors marked with "B" and/or "C" using
a proper Y quick fit connector adapters: in this case the input fuses will
have to be replaced with a suitable size for the paralleled strings.
6D
19
- 83 -
positive side and
19
string fuses, situated on each input, are not rated to
20
20
5 - Installation
negative side (-SX2, SY2
20
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pvs-120-tlFimer pvs-100-tlFimer pvs-120-tl