FIGURE and TABLE 1: Input Terminal Block Assignments
Terminal #
Earth Ground
Stud
Terminal#
Board ID
1
AC-LINE
2
AC-NEU
3
INVIN
4
INVIN(GND)*
5
Is 2
6
Is 1
7
−DCVs
8
GND*
9
A3
10
A3RTN*
11
A2
12
A2RTN*
13
A1
14
A1RTN*
15
+V3IN
16
GND*
17
+V2IN
18
GND*
19
−PWRIN*
20
+PWRIN
* CAUTION: Common to all input grounds and returns.
** Neg. DCV is not compatible with input voltages that are positive with respect to pin 8 GROUND. CAUTION:
If you intend to power from -48 VDC AND monitor -48 VDC, input power must come from an isolated DC con-
verter. If you need one, we will provide it free of charge. Contact NEWMAR: 800-854-3906 or E-mail:
techservice@newmarpower.com and request model: 48-12-1i
*** Positive ground inputs only (-48VDC)
15272 Newsboy Circle
Huntington Beach
California 92649
2 3 4
5
6 7 8 9 10 11 1213 14 15 16 17 18 19 20
1
Function/Description
Measure AC utility power, 90 to 264 VAC. This
input is isolated from all other inputs.
Measures a fl oating AC sources like an inverter, 90
to 135 VAC. INV IN (GND) is common to all GND
and RTN and -PWR IN.
Measures DC voltages across a 100mV/100A
current shunt. Is1 and Is2 inputs may be
referenced to either (+) or (-) and/or RTN/GND. 60
volt max common mode and 100mV differential
input
Measures a negative voltage with reference to
GND/RTN. -30 to -60 VDC.***
Measures a relay or switch contact closure. Short
across inputs will indicate CLOSE. Open circuit is
OPEN.
Measures a relay or switch contact closure. Short
across inputs will indicate CLOSE. Open circuit is
OPEN.
Measures a relay or switch contact closure. Short
across inputs will indicate CLOSE. Open circuit is
OPEN.
Measures a postive DC voltage, 0 to 40 volts with
reference to GND/RTN.
Measures a postive DC voltage, 0 to 40 volts with
reference to GND/RTN.
SPM-200 input power, 9 to 60 VDC, maybe
powered directly from "Negative Ground" system
only.**
www.newmartelecom.com
Default Webpage ID
Line Voltage
Inverter Voltage
Shunt Current
- Volts DC 3
Contact 3
Contact 2
Contact 1
Volts DC 2
Volts DC 1
(N/A)