Figure - NewMar SPM-200 Installation & Operation Manual

Site power monitor
Hide thumbs Also See for SPM-200:
Table of Contents

Advertisement

FIGURE 10: Logging Page
If for some reason you want to delete all the data that is in memory, click on the "Reset Logs". Caution, there is
no way to recover the data after the reset button is checked.
The check boxes sensors (Sensors page) only control what data is being graphed, not what is being logged.
The SPM-200 always logs the data from all the inputs. The data can be downloaded to a PC or a similar
machine in Comma Separated Value (CSV) format. CSV is a very simple and general way to store data in a
file. Most analysis programs, such as Microsoft Excel®, can read CSV data. So you can download all the data
in memory and analyze it with Excel®.
FIGURE 11: Display Page
The Display page is where you set the "friendly names" of the device and all the inputs, and set the units that
you want temperature displayed in. The friendly name must be no more than 19 characters.
At the top of the page select whether you want the temperature displayed in Celsius or Fahrenheit degrees.
You also have the option of entering an offset for the temperature display. As is explained on the page, you
should not change the factory setting unless your SPM-200 is mounted somewhere with very little airflow. In
that case the heat generated by the SPM-200 itself might cause the display to read a bit high.