Chapter 3 Function List - Mitsubishi Electric Melsec iQ-R60AD8-G User Manual

Analog-digital converter module
Table of Contents

Advertisement

3
FUNCTION LIST
The following table lists the functions of the A/D converter module. For further details on the functions, refer to the following.
 MELSEC iQ-R Channel Isolated Analog-Digital Converter Module User's Manual (Application)
Item
Range switching function
A/D conversion enable/disable setting function
A/D conversion
Sampling processing
method
Averaging
processing
Primary delay filter
Scaling function
Alert output
Process alarm
function
Rate alarm
Input signal error
Upper limit detection, lower limit
detection
detection, upper and lower limit
function
detection
Simple disconnection detection
Shift function
Digital clipping function
Difference conversion function
Maximum value/minimum value hold function
Logging function
Logging read function
Interrupt function
Error history function
Event history function
Offset/gain setting
Backing up, saving, and restoring offset/gain values
Description
Allows the input range of analog input to be switched for each channel. Switching the range makes
it possible to change the I/O conversion characteristics.
Controls whether to enable or disable A/D conversion for each channel. Disabling A/D conversion
for unused channels reduces the conversion cycles.
Converts analog input values into digital output values at every sampling period, storing them in
buffer memory areas.
Time average
Executes A/D conversion for the set time and performs the averaging processing on the total value
excluding the maximum and minimum values. The processed values are stored in the buffer
memory area. The number of processing times within the set time changes depending on the
number of channels where A/D conversion is enabled.
Count average
Executes A/D conversion for a set number of times and performs the averaging processing on the
total value excluding the maximum and minimum values. The processed values are stored in the
buffer memory area. The time taken to store the average value obtained by the average processing
in the buffer memory area changes depending on the number of channels where A/D conversion is
enabled.
Moving average
Averages digital output values taken at every sampling period for a specified number of times, and
stores the averaged value in the buffer memory area. The target range for averaging processing
moves at each sampling period, thereby allowing the latest digital output value to be obtained.
Smooths the transient noise of analog input depending on the set time constant. The smoothed
digital output values are stored in the buffer memory area.
Performs scale conversion on digital output values within the range from a scaling upper limit value
to a scaling lower limit value, both of which are set at desired values. This function reduces the time
and effort to create a program of the scale conversion.
Outputs an alert when a digital operation value falls within the preset alert output range.
Outputs an alert if the change rate of a digital output value is equal to or more than the rate alarm
upper limit value, or is equal to or less than the rate alarm lower limit value.
Outputs an alarm when an analog input value exceeds the preset range.
Outputs an alarm when an analog input value is 0.5V or smaller or 2mA or smaller.
Adds (shifts) a set conversion value shift amount to a digital output value, and stores the result in
the buffer memory area. A change in conversion value shift amount is reflected to the digital
operation value in real time, which facilitates fine adjustment at system start-up.
Fixes a possible digital operation value to the maximum digital output value or the minimum digital
output value when an input current or voltage exceeds the input range.
Subtracts a difference conversion reference value from a digital operation value and stores the
resulting value in the buffer memory area.
Stores the maximum and minimum values of digital operation values in the buffer memory area for
each channel.
Logs (records) digital output values or digital operation values. For each channel, 1000 points data
can be logged.
Makes it possible to store more than 1000 points of logging data without stopping logging by
transferring the device data to the file register of the CPU module during logging. This function
reduces the takt time in a test demanding high-speed conversion.
Executes an interrupt program of the CPU module when an interrupt factor such as an input signal
error or alert output is detected.
Records errors and alarms that have occurred in the A/D converter module, storing the record into
the buffer memory area. Up to 16 storage areas are provided for errors and alarms, respectively.
Collects generated errors and alarms, and performed operations in the A/D converter module as
event information into the CPU module.
Allows the correction of errors in digital output values.
The A/D converter module is capable of backing up, saving, and restoring offset/gain values of the
user range setting.
3 FUNCTION LIST
19
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: