Mitsubishi Electric Melsec iQ-R60AD8-G User Manual page 43

Analog-digital converter module
Table of Contents

Advertisement

*1 Set the offset value and gain value in the user range setting within a range satisfying the following conditions. Failure to satisfy the
conditions may not result in proper A/D conversion.
Setting range of the offset value and gain value: -10 to 10V
((Gain value) - (Offset value))  1.6V
*2 Maximum resolution in the user range setting.
*3 If an analog input value exceeds the range of digital output value, the digital output value is fixed to the maximum or minimum value.
Input range setting
1 to 5V
0 to 5V
-10 to 10V
0 to 10V
1 to 5V (extended mode)
User range setting
• Set values within the practical range of the analog input and the digital output at each input range. If the
range is exceeded, the resolution and accuracy may not fall within the range of the performance
specifications. (Do not use the values in the dotted line region in the graph of voltage input characteristics.)
• Do not set the voltage over 15V. Doing so can cause breakdown of the elements.
Digital output value
Minimum
-768
-32768
-768
-8768
-32768
Maximum
32767
36767
32767
APPENDICES
Appendix 1 I/O Conversion Characteristics
A
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r60ad16-g

Table of Contents