Delta Elektronika SM 15-400 Product Manual

Delta Elektronika SM 15-400 Product Manual

Sm6000 series
Hide thumbs Also See for SM 15-400:

Advertisement

DELTA ELEKTRONIKA B.V.
DC POWER SUPPLIES
SM6000-se ries
SM 15 - 400
SM 30 - 200
SM 45 - 140
SM 60 - 100
SM 70 - 90
SM 120 - 50
SM 300 - 20
SM 600 - 10
PROD UCT MAN UAL
Con tents:
1 - Datasheet
2 - Safety Instructions
3 - General
4 - Installation
5 - Trouble Shooting
6 - Maintenance & Calibration
7 - EC Declaration of Conformity
Vissersdijk 4, 4301 ND
www.DeltaPowerSupplies.com
Zierikzee, the Netherlands
Tel. +31 111 413656

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SM 15-400 and is the answer not in the manual?

Questions and answers

Summary of Contents for Delta Elektronika SM 15-400

  • Page 1 Vissersdijk 4, 4301 ND www.DeltaPowerSupplies.com DELTA ELEKTRONIKA B.V. Zierikzee, the Netherlands Tel. +31 111 413656 DC POWER SUPPLIES SM6000-se ries SM 15 - 400 • SM 30 - 200 • SM 45 - 140 • SM 60 - 100 •...
  • Page 2: Ac Input Ratings

    Failure to comply with the safety precautions or warnings in this document violates safety standards of design, manufacture and intended use of this equipment and may impair the built-in protections. Delta Elektronika shall not be liable for user’s failure to comply with these requirements.
  • Page 3 Unscrew the screws and remove the cover(s). • Always place the cover(s) back before connecting the unit to the mains supply again. 12 Environmental Conditions The Delta Elektronika power supplies safety approval applies to the following operating conditions: • Indoor use •...
  • Page 4: Input Voltage

    SM6000 GENERAL 3 GENERAL OUT PUT SM 15-400 SM 30-200 The SM15-400, SM30-200, SM45-140, SM60-100, SM70-90, SM120-50, SM300-20 and SM600-10 can ei ther be used as a con stant volt age source with cur rent lim it ing or as a con stant cur rent source with volt age lim it ing.
  • Page 5: An A Log Pro Gramming

    ETH / IEEE488 / RS232 / CAN / PROFI PRO GRAM MING The Delta Elektronika PSC-ETH, PSC-488, PSC-232, PSC CAN and PSC PROFI con trol lers can be fac tory in stalled in side the unit.
  • Page 6 - ferred value. * = SW1-5 only on SM300-20 / SM600-10 and on units with op tional dig i tal encoders (op tion P220). rev. June 2018 DELTA ELEKTRONIKA B.V. Page 3 - 3...
  • Page 7 Make sure to dis charge the ca pac i tors com pletely be fore us ing it again. fig. 3 - 15 In su la tion test voltages Page 3 - 4 DELTA ELEKTRONIKA B.V. rev. June 2018...
  • Page 8: Phase Loss

    The max i mum volt age be tween the out put ter mi nals and the sense in puts is lim ited at 2.5 V. For sens ing on a pul sat ing load see para graph 20) of this chap ter. rev. June 2018 DELTA ELEKTRONIKA B.V. Page 3 - 5...
  • Page 9: Series Operation

    The Mas ter / Slave com bi na tion can also be pro grammed with the in ter faces PSC-488 or the PSC-232 fig 3 - 22 Use stan dard UTP ca bles (RJ45) for Mas ter / Slave operation Page 3 - 6 DELTA ELEKTRONIKA B.V. rev. June 2018...
  • Page 10 The two fans blow through the tun nels, pe riod it can pro duce a high pitched sound. This is nor mal. where the heatsinks are sit u ated DI MEN SIONS rev. June 2018 DELTA ELEKTRONIKA B.V. Page 3 - 7...
  • Page 11: Installation

    Turn both the CV and CC po ten ti om e ter a few turns clockwise. • ca bles di rectly on the tinned out put strips. A volt age should now be pres ent on the out put. Page 4 - 1 DELTA ELEKTRONIKA B.V. rev. June 2018...
  • Page 12: Key Lock

    P598). To avoid earth loops, use an iso lated pro gram ming Lo cal sens ing. source. If this is not pos si ble, see nest para graph 8) for us ing the op tional ISO AMP CARD. rev. June 2018 DELTA ELEKTRONIKA B.V. Page 4 - 2...
  • Page 13: Battery Charger

    This can be use ful for emer - Charg ing bat tery with a cir cuit breaker in se ries. gency power sys tems. Page 4 - 3 DELTA ELEKTRONIKA B.V. rev. June 2018...
  • Page 14: Re Mote Shutdown

    Re mote CV / CC, the Key lock will be Mas ter / Slave par al lel con nec tions. ac ti vated and the out put will turn back on. rev. June 2018 DELTA ELEKTRONIKA B.V. Page 4 - 4...
  • Page 15 IEEE488/RS232 con trol ler (PSC-488 fig. 4 - 12 / PSC-232 (both δ-prod ucts) Mas ter / Slave mixed se ries - par al lel con nec - tions. Page 4 - 5 DELTA ELEKTRONIKA B.V. rev. June 2018...
  • Page 16: Troubleshooting

    To check the fuse mea sure the volt age be tween Ø and the mi nus out put, a high volt age means too much cur rent flow ing through the fuse. F27_2 = 650 mA, self re set ting. rev. June 2018 DELTA ELEKTRONIKA B.V. Page 5 - 1...
  • Page 17 5) in "op er at ing man ual". NO LEDS on Check in put. • Do not try to re pair, but send for re pair. See pre vi ous para graph • 1), 1. Page 5 - 2 DELTA ELEKTRONIKA B.V. rev. June 2018...
  • Page 18: Maintenance And Calibration

    6 - 3 Warn ing! Wrong cal i bra tion can dam age the unit. Cal i brat ing max. cur rent and off set on P597 rev. June 2018 DELTA ELEKTRONIKA B.V. Page 6 - 1...
  • Page 19 SM6000 EC DECLARATION DELTA ELEKTRONIKA B.V. Vissersdijk 4, 4301 ND www.DeltaPowerSupplies.com Zierikzee, the Netherlands Tel. +31 111 413656 DC POWER SUPPLIES EC Dec la ra tion of Con for mity - SM6000-series Delta Elektronika Vissersdijk 4 4301 ND ZIERIKZEE The Neth er lands...

Table of Contents

Save PDF