Pipework; Boiler Isolation Valve; Water Systems And Pipework - Bosch WORCESTER Danesmoor Utility Regular 2022+ 12/18 Installation, Commissioning And Servicing Instruction Manual

Floor standing oil-fired condensing boiler using conventional flue & room sealed flue
Table of Contents

Advertisement

FUEL FLOW RATE
2.5kg/h
5kg/h
Head (m)
8mmØ
8mmØ
0
100
55
0.5
95
45
1.0
80
40
1.5
70
35
2.0
60
30
2.5
45
25
3.0
35
15
3.5
25
10
[NOTE:] The table and illustration above is a guide only and does not in
any way override the de-aerator manufacturer's instructions
4.3.4

Pipework

▶ Refer to the oil supply sections Single pipe gravity feed
system: 4.3.1, Double pipe sub-gravity feed system: 4.3.2 & Single
pipe suction lift with de-aerator: 4.3.3 for oil supply pipework
configurations.
Oil supply pipework considerations:
• Lay the oil supply pipe as straight and level as possible to avoid air
pockets and unnecessary friction losses.
– Route away from the boiler access door or other hot surfaces.
• Install a manual isolating valve to the oil supply pipe, as close to the
oil storage tank as possible.
• Fit an oil strainer and water separator to the oil supply pipe, near the
oil storage tank.
– Fit an additional oil filter (70 μm max filtration size) close to the
boiler, but not inside the boiler casing.
• Fit a fire valve in accordance with BS 5410.
– The fire valve should be fitted externally to the building with the
fire valve sensor located within the appliance case.
– A fire valve with a shut off temperature of 85°C or higher must be
fitted to avoid the possibility of nuisance shut offs.
– A capillary type valve provides a neat and simple installation.
Alternatively, a fusible link or electrical system may be used.
• Under no circumstances should a combination isolating/fire valve be
used as the sole fire protection device.
4.3.5

Boiler isolation valve

▶ Use copper pipe of the correct diameter according to the information
shown in oil supply sections 4.3.1, 4.3.2 & 4.3.3.
– If using soft copper pipe (R220) with a compression fitting, an
insert must be used to prevent the pipe from collapsing or
distorting when the fitting is tightened.
▶ Slide nut [1] and olive [5] onto the oil supply pipe [4].
▶ Slide insert [3] into the pipe.
▶ Offer the pipe to the fitting [2] and tighten the nut [1].
1
5
4
3
Fig. 8
Isolation valve bracket removed for clarity
▶ Use flexible hoses to connect to the oil pump.
Greenstar Danesmoor Utility
2022+
and Utility System
10kg/h
10kg/h
8mmØ
10mmØ
26
100
23
100
20
90
17
75
14
65
11
50
8
35
5
20
2
2022+
- 6 721 846 263 (2022/01)
4.4

Water systems and pipework

NOTICE:
▶ The boiler should not be allowed to operate with a
return temperature of less than 30°C when the
system is up to operating temperature.
Oil burners cannot modulate to accommodate a
reduction in heating loads. If the heating load can be
significantly reduced due to TRV's or zoning of the
heating circuits, consideration should be given as to how
short cycling of the burner could be prevented.
Burner run times should remain greater than 2 minutes
during normal operation.
A buffer vessel or thermal store should be considered to
help prevent excessive short cycling of a single
appliance, or a low loss header could be used to divide
the heating duty between multiple lower output
appliances.
Primary system plastic pipework:
• Any plastic pipework used for the CH system must have a polymeric
barrier, complying with BS 7921 and installed to BS 5955 with
1000mm (minimum) length of copper or steel pipe connected to the
boiler.
• Plastic pipework used for underfloor heating must be correctly
controlled with a thermostatic blending valve limiting the
temperature of the circuits to approximately 50°C with 1000mm
(minimum) length of copper or steel pipe connected to the boiler,
and a 20K differential must be maintained at the appliance.
Primary system/connections/valves:
• Do not use galvanised pipes or radiators.
• All system connections, taps and mixing valves must be capable of
sustaining a pressure of 3 bar.
• Radiator valves should conform to BS 2767:10.
• All other valves should conform to BS 1010.
• An automatic bypass valve must be connected between the heating
flow and return where TRVs are used on all radiators, fitted to give at
least a 3 metre circuit when activated.
• Drain cocks are required at all the lowest points on the system.
• Air vents are required at all high points on the system.
Open vent primary system (Regular only)
• The open vent pipe (F) and feed and expansion pipe (H) must rise
continuously from the appliance.
• The feed and expansion cistern (E) must be positioned to provide a
static head (S) of at least 1 metre above the highest point in the
heating system to the water level in the feed and expansion cistern.
• Ensure adequate space is left in the expansion cistern for expansion
of the system water.
• No valve shall be fitted in the open vent pipe (F) or the feed and
expansion pipe (H).
• The open vent pipe (F) must be at least 22mmØ.
Pre-Installation
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Worcester danesmoor utility regular 2022+ 18/25Worcester danesmoor utility regular 2022+ 25/32Worcester danesmoor utility system 2022+ 12/18Worcester danesmoor utility system 2022+ 18/25Worcester danesmoor utility system 2022+ 25/327731600245 ... Show all

Table of Contents