5.5
Example of Wiring to the External Output Terminals
(EQU1 to EQU2)
When using an EQU terminal, an external power supply in the range of
10.2V DC to 30V DC is needed to operate the internal photocoupler.
Run the wires as shown below.
(1) AJ65BT-D62, AJ65BT-D62D
AJ65BT-D62, AJ65BT-D62D
(2) AJ65BT-D62D-S1
AJ65BT-D62D-S1
Point
Even when not using an EQU terminal, wire the 12/24V terminal (pin
number: 26) and the COM terminal (pin number: 27) to an external power
supply.
If they are not wired, SW0088 to SW008B (fuse blown status) of the
master module would be on.
Load
EQU1
Load
EQU2
12/24V
COM
Load
EQU1
12/24V
COM
26
10.2V to 30V
10.2V to 30V