D. Use of Elbows
Diagonal runs have both vertical and horizontal vent as-
pects when calculating the effects. Use the rise for the
vertical aspect and the run for the horizontal aspect. See
Figure 4.4.
Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216
mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A
length of straight pipe is allowed between two 45º elbows.
See Figure 4.4.
Figure 4.5 shows the vertical and horizontal offsets for
DVP or SLP elbows.
VERTICAL
Effective Length
SLP
Pipe
Inches
Millimeters
SLP4
4
SLP6
6
SLP12
12
SLP24
24
SLP36
36
SLP48
48
1219
SLP6A
3 to 6
76 to 152
SLP12A
3 to 12
76 to 305
Effective Length
DVP
Pipe
Inches
Millimeters
DVP4
4
DVP6
6
DVP12
12
DVP24
24
DVP36
36
DVP48
48
1219
DVP6A
3 to 6
76 to 152
DVP12A
3 to 12
76 to 305
Figure 4.4
18
RUN
HORIZONTAL
Rise/Run
Inches
Millimeters
102
2-3/4
152
4-1/4
305
8-1/2
610
17
914
25-1/2
34
2-1/8-4-1/4
54-108
2-1/8-8-1/2
54-216
Rise/Run
Inches
Millimeters
102
2-3/4
152
4-1/4
108
305
8-1/2
216
610
17
432
914
25-1/2
648
34
864
2-1/8-4-1/4
54-108
2-1/8-8-1/2
54-216
Heat & Glo • SL-5, SL-7, SL-9 Installation Manual • 2392-980 Rev. L • 6/17
Vent
Type
DVP
SLP
Vent Type
70
108
216
432
648
864
Figure 4.5 Vertical and Horizontal Offset for DVP and SLP Elbows
70
X
X
Inches
Millimeters
4-1/2
114
5
127
X
Inches
DVP
16-1/4
SLP
11-1/4
Y
Y
Inches
Millimeters
17
432
11-3/4
298
X
X
Millimeters
413
286