Controls; Points List; Rtm Module; Gbas Module - Trane IntelliPak SCWF 20 Installation, Operation And Maintenance Manual

Commercial self-contained signature series 20 to 110 tons
Table of Contents

Advertisement

Controls

Points List

RTM Module

Binary Inputs
Emergency stop
External auto/stop
Unoccupied/occupied
Dirty filter
VAV changeover with hydronic heat
Binary Outputs
VAV box drive max (VAV units only)
CV unoccupied mode indicator (CV units only)
Alarm
Fan run request
Water pump request (water-cooled only)
Analog Input
Airside economizer damper minimum position
Analog Output
Outside air damper actuator
Heat Module:
Analog output

GBAS Module

Binary Inputs
Demand limit contacts
Binary Outputs
Dirty filter relay
Refrigeration fail relay
Heat fail relay
Supply fan fail relay
Active diagnostics
Analog inputs
Occupied zone cooling setpoint
Occupied zone heating setpoint
Unoccupied zone cooling setpoint
Unoccupied zone heating setpoint or minimum
outside air flow setpoint
Supply air cooling setpoint
Supply air heating setpoint
Supply air static pressure setpoint
68

ECEM Module

Analog Inputs
Return air temperature
Return air humidity
I I n n a a d d d d i i t t i i o o n n , , u u n n i i t t s s w w i i t t h h a a V V O O M M h h a a v v e e : :
Binary Inputs
VOM mode A, unit off
VOM mode B, pressurize
VOM mode C, exhaust
VOM mode D, purge
VOM mode E, purge w/duct pressure control
Binary Output
V.O. relay

BCI-I option

For BACnet® Points List. refer to ACC-SVP01*-EN.

LCI-I Points List

Refer to the LonTalk™ Communications Interface for
Intellipak and Commercial Self-Contained Integration
Guide, BAS-SVP02*-EN.

Phase Monitor

Unit is equipped with phase monitor in control box.
The phase monitor will protect against phase loss,
imbalance and reversal of line voltage. If a fault occurs,
the red LED will energize. While the fault condition is
present, the phase monitor interrupts the 115V control
circuit. If no faults are observed, a green LED will be
energized.

Unit Control Components

The self-contained unit is controlled by a
microelectronic control system that consists of a
network of modules. These modules are referred to as
unit control modules (UCM). In this manual, the
acronym UCM refers to the entire control system
network.
These modules perform specific unit functions using
proportional/integral control algorithms. They are
mounted in the unit control panel and are factory wired
to their respective internal components. Each module
receives and interprets information from other unit
modules, sensors, remote panels, and customer binary
contacts to satisfy the applicable request; i.e.,
economizing, mechanical cooling, heating, ventilation.
Following is a detailed description of each module's
function.