Software settings
User-panel
Functions
4
3
The CTS150 control panel provides the following functions:
1. Setting fan speeds: 0 (off) - 1 - 2 - 3 - 4
2. Green diode: On when the unit is running
3. Setting low humidity: Can be set between 15 and 45%
4. Red diode: Flashes in the event of an alarm
Alarms
If the unit is in alarm mode, the RED diode on the CTS150 control panel will flash.
Alarm description
ID
Alarm
1.
T3 temperature sensor missing
2.
T4 temperature sensor missing
3.
T8 temperature sensor missing
4.
temperature sensor missing
5.
De-icing alarm
6.
Filter alarm
• If the unit records more than 5 de-icing registrations within 24 hours, the de-icing alarm (ID = 5) is
triggered
• To re-activate the de-icing alarm, disconnect electricity and restart the unit
• The unit shuts down when a critical alarm is active
Reset alarm:
1. Turn the fan speed selector as follows: → 0 → 4 → 0
2. Turn the selector to the fan speed required
Comfort 252 / 302 Top (English)