Time Delayed Overcurrent (51/51G/51N) - Siemens 7SR45 Argus User Manual

Self powered/dual powered non-directional overcurrent and earth fault relay
Hide thumbs Also See for 7SR45 Argus:
Table of Contents

Advertisement

1.1

Time Delayed Overcurrent (51/51G/51N)

The 51-n characteristic element provides a number of time/current operate characteristics. The element can be
defined as either an Inverse Definite Minimum Time Lag (IDMTL) or Definite Time Lag (DTL) characteristic. If an
IDMTL characteristic is required, then IEC, ANSI/IEEE and a number of manufacturer specific curves are
supported.
IDMTL characteristics are defined as "Inverse" because their tripping times are inversely proportional to the Fault
Current being measured. This makes them particularly suitable to grading studies where it is important that only
the Relay(s) closest to the fault operate. Discrimination can be achieved with minimised operating times.
To optimise the grading capability of the relay additional time multiplier, 'Follower DTL' (Fig 1-2) or 'Minimum
Operate Time' (Fig. 1 3) settings can be applied.
1000.00
100.00
10.00
1.00
0.10
0.01
1
10
Current (x Is)
Figure 1-2
©2018 Siemens Protection Devices Limited
Time Multiplier = 1
Increasing
Time
Multiplier
100
1000
IEC NI Curve with Time Multiplier and Follower DTL Applied
Chapter 7 - 7SR45 Applications Guide
1000.00
100.00
10.00
1.00
0.10
0.01
1
10
Current (x Is)
Follower
DTL
100
1000
Chapter 7 Page 7 of 10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents