Siemens 7SR45 Argus User Manual page 32

Self powered/dual powered non-directional overcurrent and earth fault relay
Hide thumbs Also See for 7SR45 Argus:
Table of Contents

Advertisement

Table 3-5
Curve type
IEC-NI
0.14
IEC-VI
13.5
IEC-EI
80
IEC-LTI
120
IEEE/ANSI - MI
----
IEEE/ANSI - VI
----
IEEE/ANSI - EI
----
Where,
I - Fault current Magnitude
Is - Pickup setting
Tm - Time multiplier
Table 3-6
Parameters
Description
Gn 51N-n Element
51N-n Block
Gn 51N-n Setting
Pick-up current
Gn 51N-n Char
Characteristics
Time Multiplier
Gn 51N-n Time
Mult
(other than DTL)
Delay
Gn 51N-n Delay
(Applicable only for
DTL)
Gn 51N-n Min
Minimum Operate
Operate
Time
Gn 51N-n
Follower DTL
Follower DTL
Gn 51N-n Reset
Reset
©2018 Siemens Protection Devices Limited
Constants for operating and reset curve characteristics
Operating time
K
α
P
0.02
----
1.0
----
2.0
----
1.0
----
----
0.02
----
2.0
----
2.0
Time Delayed Derived Earth Fault Protection (51N-n)
Default
Value
Disabled
0.5xI
IEC NI
1
5 s
0 s
0 s
0 s
Chapter 1 - 7SR45 Description of Operation
A
B
----
----
----
----
----
----
----
----
0.0515
0.114
19.61
0.491
28.2
0.1217
Min
Max
-
-
0.1xI
0.8xI
n
n
n
-
-
0.01
10
0 s
15 s
0 s
20 s
0 s
20 s
60, IEC/
0 s
ANSI
DECAY
Reset time
R
n
9.7
2
43.2
2
58.2
2
80
2
4.85
2
21.6
2
29.1
2
Step Change
-
0.01
-
0.01
0.01
0.01
0.01
1
Chapter 1 Page 29 of 48