Data Storage; Fault Records (Trip Log) - Siemens 7SR45 Argus User Manual

Self powered/dual powered non-directional overcurrent and earth fault relay
Hide thumbs Also See for 7SR45 Argus:
Table of Contents

Advertisement

3.
Card Error
In case of I/O card failure, the error message is displayed and IRF condition will be signalled.
The relay performance is not guaranteed and it should be sent to the factory.
4.
MLFB Error
If the device information data is not correct during the start up, the error message will be displayed and IRF
condition will be signalled.
In case of MLFB error the relay will not be functional and the relay should be sent to the factory.
Calibration Error
5.
The 7SR45 Argus Relay checks for the integrity of the calibration data during the start up and displays a
message in case of an error and IRF condition will be signalled.
The user can acknowledge the error message via HMI only and the default calibration data will be applied to
the relay and IRF condition will be cleared.
The relay will be functional only when the calibration error message is acknowledged. In this case, the relay
performance is not guaranteed and it should be sent to the factory for calibration.
6.
Setting Error
The 7SR45 Argus Relay checks for the integrity of the settings during the start up and displays a message in
case of an error and IRF condition will be signalled.
The user can acknowledge the error message via HMI only and the default settings will be applied to the
relay and IRF condition will be cleared.
The relay will be functional only when the setting error message is acknowledged.
NOTE:
In case Card Error and MLFB Error, the relay will not be functional and the relay should be sent to the factory.
The following table displays the error messages and the error codes in the Instrument Mode.
Errors
Setting Error
Calibration Error
MLFB Error
Card Error
Internal Supply Voltage Error
Unexpected Error
NOTE:
If a binary output is assigned to IRF, it is recommended not to use the same binary output for any other protection
function configuration.

3.19 Data Storage

The relay stores two types of data: Fault Records, Event records.
Data records are stored in the non-volatile memory. The data storage menu contains the settings for clearing
events and faults.

3.19.1 Fault Records (Trip Log)

Fault records are triggered when the protection function detects a fault condition and the trip alert message
appears on LCD to indicate that a new fault has occurred. Up to 10 fault records can be stored and displayed on
the fascia LCD.
Fault records provide a summary of relay status when the trip occurs, i.e. setting group, element issued the trip,
any phase/earth picked up, fault magnitude, LED indications, general alarm, and date and time.
Trip alert message is displayed until the fault is acknowledged by the user.
The event records and the fault records provide the full sequence of events that resulted to a trip for analysis.
Fault records are stored in a rolling buffer with the oldest faults overwritten. The fault storage can be cleared with
the DATA STORAGE > Clear Faults setting in HMI.
©2018 Siemens Protection Devices Limited
Chapter 1 - 7SR45 Description of Operation
Table 3-16
IRF
Error Code
00000001
00000010
00000100
00001000
00010000
00100000
Error Message
Load default settings!
Load default calibration!
MLFB Information Error!
Analog & IO card Error!
Chapter 1 Page 45 of 48