Carrier R080-528 Installation Instructions Manual page 43

Air-cooled chillers, 60 hz
Table of Contents

Advertisement

Cooler Leaving Fluid Temperature†
Cooler Entering Fluid Temperature**
Cooler Flow Rates 30GXN,R
080, 083
090, 093
106, 108
114
118
125
128
135
138
150, 153
160, 163
174, 178††
204, 208††
225, 228††
249, 253††
264, 268††
281††
301††
325††
350††
*Maximum ambient temperature and percent of unit capacity will vary based on
unit load and return water temperature. All models are qualified for use at
125 F (46 C). Some models may require the high ambient fan option. Contact
your local Carrier representative to obtain performance data using the Carrier
electronic catalog.
†For applications requiring cooler leaving water temperature operation at less
than 40 F (4.4 C), the units require the use of antifreeze and application may
require the special order brine option. Contact your local Carrier representative
for more information.
**For applications requiring cooler entering water temperature operation at less
than 45 F (7.2 C), contact your local Carrier representative for unit selection us-
ing the Carrier electronic catalog.
††Requires optional or accessory low ambient kit for operation below 15 F (–9 C).
All other models require the low ambient control for operation below 0° F
(– 17.8 C)
Table 3A — Unit Operating Range*
ITEM
Number of
Cooler
Passes
minus 1 pass
2
std
3
plus 1 pass
4
minus 1 pass
2
std
3
plus 1 pass
4
minus 1 pass
2
std
3
plus 1 pass
4
minus 1 pass
2
std
3
plus 1 pass
4
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
2
std
3
plus 1 pass
4
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
2
std
3
plus 1 pass
4
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
1
std
2
plus 1 pass
3
minus 1 pass
1
std
2
plus 1 pass
3
MAX
MIN
60 F (15 C)
40 F (4.4 C)
70 F (21.1 C)
45 F (7.2 C)
Max Cooler Temp
Reference
Difference
Min Flow Rate†
F
C
Gpm
13
7.4
136
20
11.1
91
27
14.8
68
13
7.4
149
20
11.1
100
27
14.8
75
13
7.4
176
20
11.1
117
27
14.8
88
13
7.4
191
20
11.1
127
27
14.8
95
10
5.6
254
20
11.1
127
30
16.7
85
13
7.4
209
20
11.1
139
27
14.8
104
10
5.6
278
20
11.1
139
30
16.7
93
13
7.4
229
20
11.1
152
27
14.8
114
10
5.6
305
20
11.1
152
30
16.7
102
10
5.6
336
20
11.1
168
30
16.7
112
10
5.6
364
20
11.1
182
30
16.7
121
10
5.6
401
20
11.1
200
30
16.7
134
10
5.6
461
20
11.1
230
30
16.7
154
10
5.6
502
20
11.1
251
30
16.7
167
10
5.6
562
20
11.1
281
30
16.7
187
10
5.6
588
20
11.1
294
30
16.7
196
10
5.6
641
20
11.1
321
30
16.7
214
10
5.6
689
20
11.1
344
30
16.7
230
10
5.6
741
20
11.1
371
30
16.7
247
10
5.6
801
20
11.1
401
30
16.7
267
NOTES:
1. The 30GXN,R units will start with loop temperatures up to 95 F (35 C).
2. Nominal flow rates required at ARI conditions 44 F (7 C) leaving fluid tempera-
ture, 54 F (12 C) entering water temperature, 95 F (35 C) ambient. Fouling fac-
tor 0.00010 ft
2
-hr-F/Btu (0.000018 m
3. To obtain proper temperature control, cooler loop fluid volume must be at least
3 gal/ton (3.23 L/kW) of chiller nominal capacity for air conditioning and at least
6 gal/ton (6.5 L/kW) for process applications or systems that must operate in
low ambient temperatures (below 32 F [0° C]).
4. Where winds of 5 mph (2.2 m/s) or greater are anticipated at outdoor ambient
temperatures below 32 F (0° C), wind baffles are required.
43
NOMINAL
Nominal
Flow Rate
L/s
Gpm
L/s
8.6
5.7
182
11.5
4.3
9.4
6.3
199
12.6
4.7
11.1
7.4
234
14.8
5.5
12.0
8.0
254
16.1
6.0
16.1
8.0
254
16.1
5.4
13.2
8.8
278
17.6
6.6
17.6
8.8
278
17.6
5.9
14.4
9.6
305
19.2
7.2
19.2
9.6
305
19.2
6.4
21.2
10.6
336
21.2
7.1
23.0
11.5
364
23.0
7.7
25.3
12.6
401
25.3
8.4
29.1
14.5
461
29.1
9.7
31.6
15.8
502
31.6
10.5
35.4
17.7
562
35.4
11.8
37.1
18.6
588
37.1
12.4
40.5
20.2
641
40.5
13.5
43.4
21.7
689
43.4
14.5
46.8
23.4
741
46.8
15.6
50.5
25.3
801
50.5
16.8
2
-K/kW).