Carrier R080-528 Installation Instructions Manual page 56

Air-cooled chillers, 60 hz
Table of Contents

Advertisement

Table 7A — Electrical Data Reduced Ambient 115 F Data (cont)
UNIT VOLTAGE
UNIT
Supplied
V-Hz
30GXN,R
(3 Ph)
Min
208/230-60
187
230-60
207
080
460-60
414
575-60
518
380-60
342
208/230-60
187
230-60
207
083
460-60
414
575-60
518
380-60
342
208/230-60
187
230-60
207
460-60
414
090
575-60
518
380-60
342
208/230-60
187
230-60
207
093
460-60
414
575-60
518
380-60
342
208/230-60
187
230-60
207
106
460-60
414
575-60
518
380-60
342
208/230-60
518
230-60
342
108
460-60
207
575-60
342
380-60
187
208/230-60
187
230-60
207
460-60
414
114
575-60
518
380-60
342
208/230-60
187
230-60
207
118
460-60
414
575-60
518
380-60
342
208/230-60
187
230-60
207
125
460-60
414
575-60
518
380-60
342
LEGEND
ICF
— Maximum Instantaneous Current Flow
MCA
— Minimum Circuit Ampacity (for wire sizing)
— Maximum Overcurrent Protection
MOCP
Rec Fuse Size — Recommended Dual-Element Fuse Amps (150% of largest
compressor rated load amps [RLA] plus 100% of remaining
compressor RLAs and sum of condenser fan full load amps
[FLAs]. Choose next largest standard fuse size.)
WD
— Wye-Delta Start
XL
— Across-the-Line Start
*Wye-delta start is standard. Across-the-line start is not available.
NOTES:
1. Main power must be supplied from a field-supplied fused electrical service with a
(factory or field-installed) disconnect located in sight from the unit.
2. Cooler heater, oil heater, and control circuit power must be supplied from a separate
source through a field-supplied disconnect. The control circuit power transformer acces-
sory may be applied to power from the main unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable supply voltage phase imbalance is voltage 2%.
5. Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent voltage imbalance.
Percent Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 240-3-60.
AB = 243 v
BC = 236 v
AC = 238 v
Average voltage =
=
POWER
# Power
SUPPLY
Supply
QTY. REQD
Max
Conductors
253
1
6
253
1
3
506
1
3
633
1
3
418
1
3
253
1
6
253
1
3
506
1
3
633
1
3
418
1
3
253
1
6
253
1
6
506
1
3
633
1
3
418
1
3
253
1
6
253
1
6
506
1
3
633
1
3
418
1
3
253
1
6
253
1
6
506
1
3
633
1
3
418
1
3
633
1
6
418
1
6
253
1
3
440
1
3
253
1
3
253
1
6
253
1
6
506
1
3
633
1
3
418
1
3
253
1
6
253
1
6
506
1
3
633
1
3
418
1
3
253
1
6
253
1
6
506
1
3
633
1
3
418
1
3
243 + 236 + 238
3
239 v
HIGH-STATIC CONDENSER FAN
ICF
MCA
MOCP
XL
WD
384.8
500
*
556.2
352.8
450
*
543.4
172.5
225
664.2
267.2
138.9
175
552.3
215.3
208.8
250
742.4
304.4
396.2
500
*
577.0
366.9
500
*
565.4
177.5
225
673.2
276.2
142.9
175
559.5
222.5
213.4
250
752.4
314.4
434.5
600
*
622.2
397.7
500
*
609.4
194.8
250
769.2
300.2
158.1
225
616.3
241.3
236.0
300
858.4
340.4
431.6
600
*
643.0
398.9
500
*
631.4
193.5
250
778.2
309.2
155.7
200
623.5
248.5
232.7
300
868.4
350.4
524.5
700
*
736.4
481.4
700
*
723.6
234.7
300
916.8
355.8
189.3
250
734.7
285.7
284.6
400
1022.2
402.2
488.3
600
*
747.7
450.2
600
*
734.2
219.1
300
922.1
361.1
176.2
250
738.6
289.6
263.8
350
1028.2
408.2
550.2
700
*
762.1
504.5
700
*
746.7
246.3
350
928.4
367.4
198.3
250
743.7
294.7
298.7
400
1036.3
416.3
542.7
700
*
802.1
502.2
600
*
786.2
243.1
300
946.1
385.1
195.8
250
758.2
309.2
292.4
400
1056.8
436.8
619.1
800
*
857.1
567.9
800
*
837.9
278.0
400
1042.5
413.5
222.7
300
835.2
332.2
335.8
450
1165.3
469.3
Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v
Maximum deviation is 4 v. Determine percent voltage imbalance:
% Voltage Imbalance
= 100 x
= 1.7%
This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.
IMPORTANT: Contact your local electric utility company immediately if the supply
voltage phase imbalance is more than 2%.
56
CONTROL CIRCUIT
Rec Fuse Size
V-Hz
MCA and
(Single Ph)
XL
WD
*
450
115-60
*
400
115-60
200
200
115-60
175
175
115-60
250
250
230-60
*
450
115-60
*
450
115-60
200
200
115-60
175
175
115-60
250
250
230-60
*
500
115-60
*
450
115-60
225
225
115-60
200
200
115-60
300
300
230-60
*
500
115-60
*
450
115-60
225
225
115-60
175
175
115-60
300
300
230-60
*
600
115-60
*
600
115-60
300
300
115-60
225
250
115-60
350
350
230-60
*
600
115-60
*
500
115-60
250
250
115-60
200
200
115-60
300
300
230-60
*
700
115-60
*
600
115-60
300
300
115-60
225
225
115-60
350
350
230-60
*
600
115-60
*
600
115-60
300
300
115-60
225
225
115-60
350
350
230-60
*
700
115-60
*
700
115-60
350
350
115-60
250
250
115-60
400
400
230-60
4
239
MOCP
30
30
30
30
15
30
30
30
30
15
30
30
30
30
15
30
30
30
30
15
30
30
30
30
15
30
30
30
30
15
30
30
30
30
15
30
30
30
30
15
30
30
30
30
15