Resolution; Analog-To-Digital Converter Filter; Input Resolution - Siemens SIMATIC 505 Installation And Operation Manual

505-2556 sixteen channel isolated thermocouple input module
Hide thumbs Also See for SIMATIC 505:
Table of Contents

Advertisement

Resolution

Analog-to-Digital
Converter Filter
SIMATIC 505–2556 Installation and Operation Guide
The module has a resolution of approximately 0.1_C, 0.2_F or exactly 0.01
millivolts.
Figure 1-12 shows the corresponding input resolution per step for each of
the input configuration modes:
Figure 1-12 Input Resolution
The SIMATIC 505–2556 features a configurable notch filter on the
analog–to–digital converters. This filter is very effective at removing
power–line frequency input noise from the analog–to–digital conversion
process. The filter frequency is configurable at jumper locatio CN10 on the
printed circuit board. With no jumper at CN10, the filter frequency is 60 Hz.
By placing the 3–pin jumper (included in an envelope packed with the
SIMATIC 505–2556) at location CN10, the filter frequency is changed to
50 Hz.
Description
1-7