Degrees Centigrade Or Degrees Fahrenheit; Scaling; Alarm Setpoints - Siemens SIMATIC 505 Installation And Operation Manual

505-2556 sixteen channel isolated thermocouple input module
Hide thumbs Also See for SIMATIC 505:
Table of Contents

Advertisement

Additional Information about Each Function (continued)
Degrees
Centigrade or
Degrees Fahrenheit

Scaling

Alarm Setpoints

3-20
Advanced Function Programming
In advanced mode the selection of degrees C or F is controlled by the
information stored and transferred to the module at WY72. The default
parameters are all zeroes which will cause the 505–2556 module to return
the value in degrees Centigrade x10. To select degrees F for the module
write a value of FFFF Hex to WY72 and use the documented transfer
procedure setting the data identification bits Y17, Y18 and Y19 to 1, 0, 0,
(See section 3.7 ).
To verify the Fahrenheit/Centigrade settings, the module reports back its
F/C status in WX57. The least significant bit (LSB) of WX57, corresponds to
channel one, while the most significant bit (MSB) corresponds to channel
16. A status bit of "1" indicates the channel is reporting in degrees F.
A status bit of "0" indicates the channel is reporting in degrees C.
Numerical Range All numbers used for scaling are expressed as signed
integers.
The numerical range for scaling is
into the module, then the value will be adjusted in the module to –32767.
Arithmetic Overflow Scaling operations may result in arithmetic
overflow. Errors of this kind for each channel may be detected with the
WX54 arithmetic overflow bits.
Overflow conditions can occur during normalization of the input value. If
the input word reaches + 32767 or –32767 before the ADC (analog-to-digital
converter) saturates, then an overrange condition occurs and the overrange
bit for that channel is set.
In a scaling operation, if the result of scaling forces the value to the PLC to
exceed 32767, the overrange bit for that channel is set.
During an overflow condition, the value to the controller defaults to
and there is no rollover of data. That is, the data does not return to zero and
beyond.
Numerical Range All numbers used for alarm setpoints are expressed as
signed integers. The numerical range for scaling is 32767. If a value of
–32768 is loaded into the module, then the value in the module is adjusted
to –32767.
32767. If a value of –32768 is loaded
SIMATIC 505–2556 Installation and Operation Guide
32767

Advertisement

Table of Contents
loading

Table of Contents