Walchem W600 Instruction Manual page 58

Modbus
Hide thumbs Also See for W600:
Table of Contents

Advertisement

5.3.7.6 Pulse Relay Output / Lag Output Control Mode Address Map
Address
Field
0
Time On
1
2
Total Time
3
4
Percent Output
5
6
Setpoint 1 ‡
7
8
Setpoint 2 ‡
9
10
Deadband ‡
11
12
Activation Delay
Time †‡
13
14
Wear Level Cycle
Time †‡
15
16
Current Activation
Time †‡
17
18
Current Wear Level
Cycle Time †‡
19
No. of Activated
20
Outputs †‡
21
22
Output Time Limit
23
24
25
26
27
28
29
Reset Output
30
Timeout
31
32
Reset Time Total
33
HOA Setting
34
Status
35
Alarm Bitfield
† Field is only defined for Lag Outputs configured as the "Last Lag" in the chain.
‡ Field is only meaningful for certain configurations of Lead-Lag chains.
Pulse Relay Output / Lag Output Control Mode Address Map
Data Encoding
32-Bit Integer
32-Bit Integer
32-Bit Float
32-Bit Float
32-Bit Float
32-Bit Float
32-Bit Integer
32-Bit Integer
32-Bit Integer
32-Bit Integer
16-Bit Integer
32-Bit Integer
Boolean
Boolean
16-Bit Integer
16-Bit Status
16-Bit Bitfield
Permissions
Read
Read
Read
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read
Read
Read
Read/Write
Read/Write
Write 1 to Reset Output Timeout
Read/Write
Read/Write
Read
See
Read
58
Value
Seconds
Seconds
Percent
Input Sensor Units
Input Sensor Units
Input Sensor Units
0 – 86,399 Seconds
10 – 86,399 Seconds
Seconds
Seconds
Count
0 – 86,399 Seconds
Write 1 to Reset Time Total
0 = Hand, 1 = Off,
2 = Auto Mode
See
5.4 Status Register Codes
5.5.6 Relay Output Alarm Bitfield
When accessed as a Coil,
Returns 1 if any alarm is active

Advertisement

Table of Contents
loading

This manual is also suitable for:

W900