Terminal Assignment; Inputs - Siemens SIRIUS 3SK1 Manual

Industrial controls safety engineering safety relays
Hide thumbs Also See for SIRIUS 3SK1:
Table of Contents

Advertisement

3SK1 devices
5.1 3SK1 standard
5.1.4.4

Terminal assignment

A1
A2
IN1
IN2
INS
INF
INK
T1
T2
Q1
Q2
QM1
5.1.4.5

Inputs

The device has five inputs for safe signal processing: IN1, IN2, INS, INF, INK:
● IN1: sensor input channel 1
● IN2: sensor input channel 2
● INS: START pushbutton circuit (start after rising and falling edge)
● INF: feedback circuit (checked for closed state: before switching on)
● INK: cascading circuit (cascading input/normal switching duty)
● The cascading circuit is AND-connected with the IN1 and IN2 sensor inputs.
● START button circuit and cascading circuit are activated with a static +24 V DC signal.
● With cross-circuit detection activated, the following inputs are checked for cross-circuits
and short-circuits to P: IN1/T1 to IN2/T2 and INF/T2. The inputs then receive their
supplies from the test outputs T1 and T2.
● If "without cross-circuit detection" is set on the device, inputs IN1 and IN2 are not
checked for cross-circuits. Inputs IN1 and IN2 must not be supplied via T1/T2 here,
otherwise a fault will be generated via input INF. It is therefore essential that inputs IN1
and IN2 are supplied via an external + 24 V DC current source from which the device is
also supplied.
● If the unit is parameterized to 2 x 1-channel with DIP switch 3, the sensor circuit that is
not used (T1/IN1 or T2/IN2) must be bypassed.
58
Terminal
+
-
Sensor channel 1
Sensor channel 2
START pushbutton circuit
Feedback circuit
Cascading circuit
Test output 1 (for IN1)
Test output 2 (for IN2, INF)
Semiconductor output 1 (switching to P potential, 24 V DC)
Semiconductor output 2 (switching to P potential, 24 V DC)
Semiconductor signaling circuit 1 (switching to P potential, 24 V DC)
Explanation
SIRIUS 3SK1 safety relays
Manual, 06/2018, A5E02526190021A/RS-AD/004