Display and diagnostics
12.4 Diagnostics
Safety mode
Explanation
No startup testing
Device ready for operation, all outputs OFF
Device ready for operation, all outputs ON
Device ready for operation, instantaneous outputs OFF,
time-delayed outputs ON
For monitored start: START button not yet pressed
With input expansion: missing enabling signal of input
expansion
Configuration has been changed (PAR, DIP switch,
potentiometer)
For 1x2-channel: Simultaneity violated
For two-hand operation: time monitoring violated
Short-circuit test clock output T1 or T2
For monitored start: START button was pressed too long
or has a short-circuit
Feedback circuit error
Dependent on device status
1)
Green flashing DEVICE LED: No startup testing
2)
Error mode
Explanation
Device fault (restart possible by pressing the SET/RESET
button)
Group error (restart possible by pressing the SET/RESET
button)
Group error, cross-circuit at the input (restart possible by
pressing the SET/RESET button)
System stop (restart possible by disconnecting and re-
connecting the operating voltage)
On time-delayed devices, the LED flashes green/yellow provided the time-delayed outputs are still switched on
3)
202
DEVICE
OUT
Green
Off
flashing
Green
Off
Green
Green
Green
Green/yellow
flashing
Green
Off
Green
Off
Green/yellow
1)
flashing
Green
Off
Green
Off
2)
Green
Yellow
flashing
Green
Green
flashing
DEVICE
OUT
Red
Off
3)
Off
Off
3)
3)
Off
Off
3)
3)
Red
Off
3)
Manual, 06/2018, A5E02526190021A/RS-AD/004
IN
SF
Off
Off
Off
Off
Green
Off
Off
Off
Green
Off
flashing
Yellow
Off
flashing
1)
1)
Green
Red flashing
flashing
Yellow
Red flashing
flashing
Off
Red flashing
Green
Red flashing
IN
SF
Off
Off
3)
3)
Off
Red
3)
Flashing
Red
yellow
3)
Off
Red
3)
SIRIUS 3SK1 safety relays