Control Settings; Access Level; Dip Switch Settings - Bosch Heatronic 4000 Installation & Operating Instructions Manual

4 boiler control, dhw, bacnet and modbus io heatronic 4000 2014/04 en-us
Hide thumbs Also See for Heatronic 4000:
Table of Contents

Advertisement

Control Settings

Access Level

The access level restricts the number of menus & items that
can be accessed by the user. The Access Level setting is
found in the Toolbox menu. Select the appropriate access
level for the people who work with the control on a regular
basis. There are three Access Level settings:
• User (USER): Select this access level to limit the number
of items available to the end user.
• Installer (INST): Select this access level to limit some of the

DIP Switch Settings

DIP
PrimPump FlowProof/Off
Comb Air Proof / Off
Off / Exercise
Setback / Off
BTC461503101C | 6720810369 (2018/03)
Description
Lock / Unlock & Access Levels
Use this DIP switch to lock & unlock the Access Level of the Heatronic 4000.
For details, see above.
• Once unlocked, the access level can be changed in the Toolbox menu.
• Once locked, the access level in all devices cannot be viewed or
changed.
• When the control is locked a small segment representing a padlock is show
in the display.
Prim Pump Flow Proof / Off
Use this DIP switch to select whether or not the Prim Pump Flow Proof feature
is to be used.
• If the Prim Pump Flow Proof feature is being used, set the DIP switch to
the Prim Pump Flow Proof position. The control must receive an external
Prim Pump Flow Proof within a period of time once a primary pump is
turned on.
• If the Prim Pump Flow Proof feature is not being used, set the DIP switch
to the Off position.
Comb Air Proof / Off
Use this DIP switch to select whether or not the Comb Air Proof feature is to
be used.
• If the Comb Air Proof feature is being used, set the DIP switch to the Comb
Air Proof position. The control must receive an external Comb Air Proof
within a period of time once the C.A. damper is turned on.
• If the Comb Air Proof feature is not being used, set the DIP switch to the
Off position.
Off / Exercise
Use this DIP switch to select whether or not the control is to exercise all pumps
for 10 seconds every three days of inactivity.
Setback / Off
Use this DIP switch to select whether or not the control is to follow a
schedule.
31 of 60
items available to the installer. This is the factory default
access level. The Heatronic 4000 defaults to the 'Installer'
access level after 24 hours.
• Advanced (ADV): Select this access level to have complete
access to all of the items.
: the Lock / Unlock switch on the front of
Requirements
the control must be set the Unlock position to change the
access level.
Default
Unlocked
Off
Off
Exercise
Off
Heatronic 4000